Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 18, 2021, 11:07 AM
  • A 0202_A 0201_02182021_031235.mp4

Date
02/18/2021
W/O
875111
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00323
PipeID
P08138
Time
3:07 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8487
Sewer Name
A JOA-1A LOS COYOTES WRP INTERCEPTOR
City
SOUTH GATE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
29
Purpose
Routine Assessment
Project
RFIR_WO_875111_TV30023_FEB2021
Sewer Type
Siphon
Material
Reinforced Concrete Pipe
Shape
Circular
Height
78 in.
Width
39 in.
Upstream MH
A 0202
Downstream MH
A 0201
Dir. of Survey
Downstream
Length Surveyed
16.6 ft.
Total Length
16.6 ft.
Structural Index
4
Structural Quick
5133
Structural Rating
14
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
20
Pipe schematic from manhole A 0202 to A 0201
MH: A 0202MH: A 0201downstream0 ft. MWM - Water Mark, 100 %of cross sectional area0 ft. MWL - Water Level, 100 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 02022 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start16 ft. LD - Alignment Down, 45 %16.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish16.6 ft. MSA - Survey Abandoned - VIEW OF DOWNLEG OF U/S SIPHON.16.6 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO

Observation photos (3)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Survey Abandoned - VIEW OF DOWNLEG OF U/S SIPHON.

    16.6 ft. - Survey Abandoned - VIEW OF DOWNLEG OF U/S SIPHON.

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO

    16.6 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO

Observations (9)

DistanceCodeObservation
16.6SAP
16.6MSAVIEW OF DOWNLEG OF U/S SIPHON.
0MWM
16.6SRV
0MWL
16LD
2DAGS
2.1SAP
0AMHA 0202

Properties (8)

additional_info
630074021721201
custom_field_three
AGGREGATE PROJECTING/REINFORCEMENT VISIBLE
custom_field_two
2
customer
1
datetime
2021-02-18T03:07:19-08:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
27983