Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 3, 2021, 05:47 PM
  • A 0822_A 0439_03032021_095545.mp4

Date
03/03/2021
W/O
875111
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00323
PipeID
P08162
Time
9:47 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8651
Sewer Name
A JOA-1A LOS COYOTES WRP INTERCEPTOR
City
BELL GARDENS
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
26
Purpose
Routine Assessment
Project
RFIR_WO_875111_TV30023_FEB2021
Sewer Type
Siphon
Material
Reinforced Concrete Pipe
Shape
Circular
Height
60 in.
Width
36 in.
Upstream MH
A 0822
Downstream MH
A 0439
Dir. of Survey
Downstream
Length Surveyed
5.2 ft.
Total Length
5.2 ft.
Structural Index
3
Structural Quick
5131
Structural Rating
10
O&M Index
5
O&M Quick
5141
O&M Rating
9
Overall Index
4
Overall Quick
Overall Rating
19
Pipe schematic from manhole A 0822 to A 0439
MH: A 0822MH: A 0439downstream0 ft. MWM - Water Mark, 100 %of cross sectional area0 ft. MWL - Water Level, 100 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 08222 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES4.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES4.6 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES5.1 ft. LD - Alignment Down, 45 %5.2 ft. MSA - Survey Abandoned - VIEW OF SIPHON DOWNLEG

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

    4.6 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES

    4.6 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (8)

DistanceCodeObservation
0MWM
5.2MSAVIEW OF SIPHON DOWNLEG
2SSS
4.6SAP
5.1LD
4.6SRC
0MWL
0AMHA 0822

Properties (7)

additional_info
630138030321062
custom_field_three
REINFORCEMENT CORRODED
custom_field_two
2
customer
1
datetime
2021-03-03T09:47:45-08:00
documentation
PROPIPE
is_lateral_inspection
false