Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 26, 2021, 05:59 AM
  • A 0163_A 1291_02252021_230217.mp4

Date
02/25/2021
W/O
875111
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00323
PipeID
P26313
Time
9:59 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8491
Sewer Name
A JOA-1A LOS COYOTES WRP INTERCEPTOR
City
BELLFLOWER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
37
Purpose
Routine Assessment
Project
RFIR_WO_875111_TV30023_FEB2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
78 in.
Width
78 in.
Upstream MH
A 0163
Downstream MH
A 1291
Dir. of Survey
Downstream
Length Surveyed
778.7 ft.
Total Length
778.7 ft.
Structural Index
3
Structural Quick
3}2^
Structural Rating
1240
O&M Index
2
O&M Quick
2^00
O&M Rating
310
Overall Index
3
Overall Quick
Overall Rating
1550
Pipe schematic from manhole A 0163 to A 1291
MH: A 0163MH: A 1291downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 01632 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.3 ft. MGO - General Observation - 55% MAG COAT2.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start776 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish776 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish776 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish778.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish778.7 ft. AMH - Downstream Manhole, Survey Ends - A 1291

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.9 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
0MWL
776SSS
778.7SAP
776SAP
2SSS
778.7AMHA 1291
0MWM
0AMHA 0163
776DAGS
2.9SAP
2.3MGO55% MAG COAT
2DAGS
2SAP

Properties (7)

additional_info
630074022521201
custom_field_three
AGGREGATE PROJECTING
custom_field_two
2
customer
1
datetime
2021-02-25T21:59:27-08:00
documentation
PROPIPE
is_lateral_inspection
false