Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 18, 2021, 11:34 AM
  • A 0200B_A 0200A_02182021_033657.mp4

Date
02/18/2021
W/O
875111
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00323
PipeID
P08136
Time
3:34 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8487
Sewer Name
A JOA-1A LOS COYOTES WRP INTERCEPTOR
City
SOUTH GATE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
29
Purpose
Routine Assessment
Project
RFIR_WO_875111_TV30023_FEB2021
Sewer Type
Siphon
Material
Reinforced Concrete Pipe
Shape
Circular
Height
78 in.
Width
39 in.
Upstream MH
A 0200B
Downstream MH
A 0200A
Dir. of Survey
Downstream
Length Surveyed
13.3 ft.
Total Length
13.3 ft.
Structural Index
3
Structural Quick
3222
Structural Rating
10
O&M Index
3
O&M Quick
4122
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
18
Pipe schematic from manhole A 0200B to A 0200A
MH: A 0200BMH: A 0200Adownstream0 ft. MWL - Water Level, 100 %of cross sectional area0 ft. MGO - General Observation - ROACHES @ MH0 ft. AMH - Upstream Manhole, Survey Begins - A 0200B0 ft. MWM - Water Mark, 100 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - 55% MAG COAT2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start11 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish11 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish13.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish13.2 ft. LD - Alignment Down, 45 %13.3 ft. MSA - Survey Abandoned - VIEW OF DOWNLEG OF U/S SIPHON.

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Survey Abandoned - VIEW OF DOWNLEG OF U/S SIPHON.

    13.3 ft. - Survey Abandoned - VIEW OF DOWNLEG OF U/S SIPHON.

Observations (13)

DistanceCodeObservation
2SSS
2.2SAP
11SSS
0MWL
0MGOROACHES @ MH
13.1SAP
0AMHA 0200B
0MWM
13.2LD
2MGO55% MAG COAT
13.3MSAVIEW OF DOWNLEG OF U/S SIPHON.
11DAGS
2DAGS

Properties (8)

additional_info
630074021721201
custom_field_three
AGGREGATE PROJECTING
custom_field_two
5
customer
1
datetime
2021-02-18T03:34:14-08:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
27983