Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 24, 2021, 06:35 PM
  • A 0155_A 0154_02242021_120145.mp4

Date
02/24/2021
W/O
875111
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00323
PipeID
P08092
Time
10:35 AM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8526
Sewer Name
A JOA-1A LOS COYOTES WRP INTERCEPTOR
City
BELLFLOWER
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
37
Purpose
Routine Assessment
Project
RFIR_WO_875111_TV30023_FEB2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
78 in.
Width
42 in.
Upstream MH
A 0155
Downstream MH
A 0154
Dir. of Survey
Downstream
Length Surveyed
979.2 ft.
Total Length
979.2 ft.
Structural Index
3
Structural Quick
5f3f
Structural Rating
1950
O&M Index
2
O&M Quick
2f00
O&M Rating
390
Overall Index
3
Overall Quick
Overall Rating
2340
Pipe schematic from manhole A 0155 to A 0154
MH: A 0155MH: A 0154downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 01552 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - 70% MAG COAT2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start977 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish977 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish977 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish977 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish979.2 ft. AMH - Downstream Manhole, Survey Ends - A 0154

Observation photos (1)

  • General Observation - 70% MAG COAT

    2 ft. - General Observation - 70% MAG COAT

Observations (13)

DistanceCodeObservation
2SRV
0MWL
977DAGS
2DAGS
2SSS
979.2AMHA 0154
0MWM
977SSS
977SRV
2MGO70% MAG COAT
977SAV
2SAV
0AMHA 0155

Properties (8)

additional_info
630138022421061
custom_field_three
LIGHT GREASE
custom_field_two
3
customer
1
datetime
2021-02-24T10:35:35-08:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
27936