Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 1, 2021, 05:26 PM
  • 29 0342_29 0341_03012021_105352.mp4

Date
03/01/2021
W/O
880264
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z01017
PipeID
P24362
Time
9:26 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7847
Sewer Name
29 PACIFIC COAST HIGHWAY SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
04
Purpose
Capital Improvement Program Assesment
Project
RFIR_WO_880264_TV29105_MAR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0342
Downstream MH
29 0341
Dir. of Survey
Downstream
Length Surveyed
145.3 ft.
Total Length
145.3 ft.
Structural Index
2
Structural Quick
3321
Structural Rating
12
O&M Index
3
O&M Quick
3121
O&M Rating
5
Overall Index
2
Overall Quick
Overall Rating
17
Pipe schematic from manhole 29 0342 to 29 0341
MH: 29 0342MH: 29 0341downstream0 ft. AMH - Upstream Manhole, Survey Begins - 29 03420 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. MWL - Water Level, 0 %of cross sectional area2.2 ft. MGO - General Observation - MISC. STAINING7.5 ft. CC - Crack Circumferential, from 12 to 12 o'clock, within 8 inches of joint: NO17.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"23 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"51 ft. CS - Crack Spiral, from 10 to 11 o'clock, within 8 inches of joint: YES55.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"68.3 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES112.9 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"114.6 ft. CM - Crack Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES118.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"131.8 ft. CM - Crack Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES142.6 ft. DSF - Deposits Settled Fine, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES144.4 ft. TBI - Tap Break-In Intruding, at 03 o'clock, -, -, within 8 inches of joint: NO, 6", 1"145.3 ft. MSA - Survey Abandoned - UNABLE TO PASS LATERAL

Observation photos (7)

  • Crack Circumferential, from 12 to 12 o'clock, within 8 inches of joint: NO

    7.5 ft. - Crack Circumferential, from 12 to 12 o'clock, within 8 inches of joint: NO

  • Crack Spiral, from 10 to 11 o'clock, within 8 inches of joint: YES

    51 ft. - Crack Spiral, from 10 to 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    68.3 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES

    114.6 ft. - Crack Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES

    131.8 ft. - Crack Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES

  • Deposits Settled Fine,  5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES

    142.6 ft. - Deposits Settled Fine, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES

  • Tap Break-In Intruding, at 03 o'clock, -, -, within 8 inches of joint: NO, 6", 1"

    144.4 ft. - Tap Break-In Intruding, at 03 o'clock, -, -, within 8 inches of joint: NO, 6", 1"

Observations (17)

DistanceCodeObservation
55.2TF
2.2MGOMISC. STAINING
131.8CM
114.6CM
144.4TBI
142.6DSF
145.3MSAUNABLE TO PASS LATERAL
0AMH29 0342
17.4TF
68.3CM
118.5TFC
23TF
0MWM
51CS
112.9TFC
0MWL
7.5CC

Properties (7)

additional_info
630138030121061
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-03-01T09:26:00-08:00
documentation
PROPIPE
is_lateral_inspection
false