Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 26, 2021, 08:40 PM
  • 29 0340_29 0338_02262021_140454.mp4

Date
02/26/2021
W/O
880264
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z01017
PipeID
P24360
Time
12:40 PM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7846
Sewer Name
29 PACIFIC COAST HIGHWAY SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
04
Purpose
Capital Improvement Program Assesment
Project
RFIR_WO_880264_TV29105_MAR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0338
Downstream MH
29 0340
Dir. of Survey
Upstream
Length Surveyed
250.3 ft.
Total Length
250.3 ft.
Structural Index
3
Structural Quick
4133
Structural Rating
15
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
15
Pipe schematic from manhole 29 0338 to 29 0340
MH: 29 0338MH: 29 0340upstream0 ft. AMH - Upstream Manhole, Survey Ends - 29 034013.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"26.9 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"34.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"64 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"93.8 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"98.3 ft. CS - Crack Spiral, from 12 to 04 o'clock, within 8 inches of joint: YES114.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"141.3 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"153.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"163.8 ft. FM - Fracture Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES164.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"178.1 ft. CM - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES209.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"211.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"219.1 ft. CM - Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES225 ft. CM - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES249.9 ft. MGO - General Observation - MISC. STAINING250.3 ft. MWL - Water Level, 5 %of cross sectional area250.3 ft. AMH - Downstream Manhole, Survey Begins - 29 0338250.3 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK250.3 ft. MWM - Water Mark, 10 %of cross sectional area

Observation photos (7)

  • General Observation - MISC. STAINING

    0.4 ft. - General Observation - MISC. STAINING

  • Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

    25.3 ft. - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES

    31.2 ft. - Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    38.7 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

    72.2 ft. - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES

    86.5 ft. - Fracture Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 12 to 04 o'clock, within 8 inches of joint: YES

    152 ft. - Crack Spiral, from 12 to 04 o'clock, within 8 inches of joint: YES

Observations (22)

DistanceCodeObservation
38.7TFC
85.5TFC
0MWL
156.5TBA
25.3CM
0.4MGOMISC. STAINING
0AMH29 0338
41.1TFC
186.3TFC
250.3AMH29 0340
223.4TF
216TFC
0MGOCONNECTION AT MH, 9 O'CLOCK
31.2CM
236.5TFC
86.5FM
72.2CM
97.1TFC
0MWM
135.9TFC
109TF
152CS

Properties (7)

additional_info
630075022621062
custom_field_three
CRACKS, FRACTURES
custom_field_two
2
customer
1
datetime
2021-02-26T12:40:28-08:00
documentation
PROPIPE
is_lateral_inspection
false