Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 26, 2021, 09:11 PM
  • 29 0338_29 0337_02262021_144908.mp4

Date
02/26/2021
W/O
880264
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z01017
PipeID
P24357
Time
1:11 PM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7846
Sewer Name
29 PACIFIC COAST HIGHWAY SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
04
Purpose
Capital Improvement Program Assesment
Project
RFIR_WO_880264_TV29105_MAR2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0338
Downstream MH
29 0337
Dir. of Survey
Downstream
Length Surveyed
375.2 ft.
Total Length
375.2 ft.
Structural Index
3
Structural Quick
433M
Structural Rating
228
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
228
Pipe schematic from manhole 29 0338 to 29 0337
MH: 29 0338MH: 29 0337downstream0 ft. AMH - Upstream Manhole, Survey Begins - 29 03380 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK1 ft. MGO - General Observation - MISC. STAINING36.1 ft. TFB - Tap Factory Made Abandoned, at 03 o'clock, -, within 8 inches of joint: NO, 6" - DEBRIS40.4 ft. MGO - General Observation - PIPE MATERIAL IS NRCP NOT VCP41.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start45.6 ft. CM - Crack Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES50.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES60.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES90.4 ft. TFB - Tap Factory Made Abandoned, at 10 o'clock, -, within 8 inches of joint: NO, 6" - DEBRIS167 ft. TFB - Tap Factory Made Abandoned, at 02 o'clock, -, within 8 inches of joint: NO, 6" - DEBRIS177.2 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"193.9 ft. FH2 - Fracture Longitudinal Hinge, 2, from 03 to 09 o'clock, within 8 inches of joint: YES199.1 ft. FS - Fracture Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES210.6 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"240.9 ft. TFB - Tap Factory Made Abandoned, at 10 o'clock, -, within 8 inches of joint: NO, 6"251.4 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"285.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: NO329.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES333.5 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 4"335.4 ft. TFB - Tap Factory Made Abandoned, at 02 o'clock, -, within 8 inches of joint: NO, 6"337 ft. FM - Fracture Multiple, from 04 to 08 o'clock, within 8 inches of joint: YES358.5 ft. TFB - Tap Factory Made Abandoned, at 10 o'clock, -, within 8 inches of joint: NO, 6"365.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES372.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish375.2 ft. AMH - Downstream Manhole, Survey Ends - 29 0337375.2 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK

Observation photos (10)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    41.2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES

    45.6 ft. - Crack Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    50.6 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    60.9 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal Hinge, 2, from 03 to 09 o'clock, within 8 inches of joint: YES

    193.9 ft. - Fracture Longitudinal Hinge, 2, from 03 to 09 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES

    199.1 ft. - Fracture Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: NO

    285.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: NO

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    329.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 04 to 08 o'clock, within 8 inches of joint: YES

    337 ft. - Fracture Multiple, from 04 to 08 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    365.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (29)

DistanceCodeObservation
40.4MGOPIPE MATERIAL IS NRCP NOT VCP
335.4TFB
177.2TFA
199.1FS
285.9CM
372.7SAV
41.2SAV
0AMH29 0338
45.6CM
193.9FH2
50.6CM
240.9TFB
0MWL
251.4TF
375.2AMH29 0337
375.2MGOCONNECTION AT MH, 9 O'CLOCK
167TFBDEBRIS
0MWM
36.1TFBDEBRIS
365.2FM
90.4TFBDEBRIS
210.6TBA
1MGOMISC. STAINING
0MGOCONNECTION AT MH, 9 O'CLOCK
358.5TFB
333.5TB
60.9CM
329.5CM
337FM

Properties (7)

additional_info
630075022621062
custom_field_three
FRACTURES, AGGREGATE VISIBLE
custom_field_two
2
customer
1
datetime
2021-02-26T13:11:11-08:00
documentation
PROPIPE
is_lateral_inspection
false