Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 1, 2021, 10:51 AM
  • H 0619_H 0618_03012021_033648.mp4

Date
03/01/2021
W/O
875032
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00191
PipeID
P11037
Time
2:51 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8623
Sewer Name
H JOINT OUTFALL H - UNIT 8H
City
BALDWIN PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
24
Purpose
Routine Assessment
Project
WO_875032_TV15175_FEB2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
39 in.
Width
39 in.
Upstream MH
H 0619
Downstream MH
H 0618
Dir. of Survey
Downstream
Length Surveyed
477.8 ft.
Total Length
477.8 ft.
Structural Index
2
Structural Quick
322R
Structural Rating
196
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
196
Pipe schematic from manhole H 0619 to H 0618
MH: H 0619MH: H 0618downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 06190 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK2.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.6 ft. MGO - General Observation - MAG COAT2.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start69 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 10"116.7 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 10"141.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"213.3 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 10"294.3 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6"326.5 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 8"477.8 ft. AMH - Downstream Manhole, Survey Ends - H 0618477.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish477.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (7)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COAT

    2.6 ft. - General Observation - MAG COAT

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 10"

    69 ft. - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 10"

  • Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 10"

    116.7 ft. - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 10"

  • Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 10"

    213.3 ft. - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 10"

  • Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 8"

    326.5 ft. - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 8"

Observations (16)

DistanceCodeObservation
0MWL
477.8AMHH 0618
326.5TB
2.6SAP
0AMHH 0619
116.7TBA
294.3TF
2.6MGOMAG COAT
0MWM
2.6SSS
213.3TBA
69TBA
477.8SSS
141.2TFC
477.8SAP
0MGOCONNECTION AT MH, 3 O'CLOCK

Properties (6)

custom_field_three
AGGREGATE PROJECTING, SPALLING
custom_field_two
3
customer
1
datetime
2021-03-01T02:51:50-08:00
documentation
PRO PIPE
is_lateral_inspection
false