Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 19, 2021, 10:36 AM
  • 29 0193_29 0173_02192021_025609.mp4

Date
02/19/2021
W/O
875678
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z01025
PipeID
P24091
Time
2:36 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8612
Sewer Name
29 28TH STREET SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
02
Purpose
Capital Improvement Program Assesment
Project
RFIR_WO_875678_TV29101_FEB2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0193
Downstream MH
29 0173
Dir. of Survey
Downstream
Length Surveyed
326.4 ft.
Total Length
326.4 ft.
Structural Index
3
Structural Quick
413K
Structural Rating
190
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
190
Pipe schematic from manhole 29 0193 to 29 0173
MH: 29 0193MH: 29 0173downstream0 ft. AMH - Upstream Manhole, Survey Begins - 29 01930 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area9.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES18 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start40.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"42.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"51.3 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 8"90.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"93.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"140.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"143.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"188 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"190.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"216.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES217 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 8"238 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"240.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"288.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"290.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 8"324.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish326.4 ft. AMH - Downstream Manhole, Survey Ends - 29 0173

Observation photos (5)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    9.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    18 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 8"

    51.3 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 8"

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    216.4 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 8"

    217 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 8"

Observations (22)

DistanceCodeObservation
190.7TFC
238TFC
9.4CM
216.4FM
90.5TFC
93.2TFC
217TB
240.9TFC
40.7TFC
324.3CM
0AMH29 0193
0MWL
140.8TFC
0MWM
42.7TFC
188TF
18CM
51.3TB
143.2TFC
290.9TF
288.6TFC
326.4AMH29 0173

Properties (7)

additional_info
BROKEN PIPE
custom_field_three
FRACTURE, CRACKS
custom_field_two
2
customer
1
datetime
2021-02-19T02:36:24-08:00
documentation
PRO PIPE
is_lateral_inspection
false