Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 12, 2021, 10:54 AM
  • 05 1316_05 1315_03122021_043059.mp4

Date
03/12/2021
W/O
880062
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00452
PipeID
P06532
Time
2:54 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8660
Sewer Name
05 GRAMERCY PLACE TRUNK, SECTION 3
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
18
Purpose
Routine Assessment
Project
RFIR_WO_880062_TV05348_MAR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Width
15 in.
Upstream MH
05 1316
Downstream MH
05 1315
Dir. of Survey
Downstream
Length Surveyed
450.8 ft.
Total Length
450.8 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
6
Pipe schematic from manhole 05 1316 to 05 1315
MH: 05 1316MH: 05 1315downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 13160 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area2.2 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.2 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start11.2 ft. MGO - General Observation - STEAM IN SEWER89.2 ft. MGP - General Photograph - DEPOSITS298.8 ft. CS - Crack Spiral, from 11 to 12 o'clock, within 8 inches of joint: YES448.9 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish450.8 ft. AMH - Downstream Manhole, Survey Ends - 05 1315450.8 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (3)

  • Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2.2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Photograph - DEPOSITS

    89.2 ft. - General Photograph - DEPOSITS

  • Crack Spiral, from 11 to 12 o'clock, within 8 inches of joint: YES

    298.8 ft. - Crack Spiral, from 11 to 12 o'clock, within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
0AMH05 1316
2.2DSC
2.2DAGS
89.2MGPDEPOSITS
298.8CS
450.8AMH05 1315
448.9DSC
0MWM
11.2MGOSTEAM IN SEWER
0MWL
450.8DAGS

Properties (7)

additional_info
630138031221231
custom_field_three
MINOR CRACKS
custom_field_two
3
customer
1
datetime
2021-03-12T02:54:03-08:00
documentation
PROPIPE
is_lateral_inspection
false