- Date
- 04/09/2021
- W/O
- 0885862
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00690
- PipeID
- P14210
- Time
- 2:19 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- H1772
- Sewer Name
- 18 NORTH NORWALK TRUNK
- City
- NORWALK
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 18
- Page No.
- 25
- Purpose
- Capital Improvement Program Assesment
- Project
- 20210409MDM_NORTH_NORWALK_TRUNK
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 15 in.
- Upstream MH
- 18 0376
- Downstream MH
- 18 0375
- Dir. of Survey
- Downstream
- Length Surveyed
- 205.7 ft.
- Total Length
- 205.7 ft.
- Structural Index
- 2
- Structural Quick
- 382B
- Structural Rating
- 50
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 50
Pipe schematic from manhole 18 0376 to 18 0375 Observation photos (4)

155.8 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

175.3 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H

196.5 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

200.5 ft. - Fracture Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES - SLIGHT WITH A CHIP