Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 6, 2021, 09:44 AM
  • 05 1301_05 1300_462021_024900.mp4

Date
04/06/2021
W/O
0880700
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00452
PipeID
P06515
Time
2:44 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1766
Sewer Name
05 GRAMERCY PLACE TRUNK, SECTION 3
City
GARDENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
21
Purpose
Capital Improvement Program Assesment
Project
20210406MDM_GRAMERCY_PLACE_TRUNK_SECTION_3
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
05 1301
Downstream MH
05 1300
Dir. of Survey
Downstream
Length Surveyed
392.8 ft.
Total Length
392.8 ft.
Structural Index
2
Structural Quick
2400
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
8
Pipe schematic from manhole 05 1301 to 05 1300
MH: 05 1301MH: 05 1300downstream0 ft. AMH - Upstream Manhole, Survey Begins - 2:45AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT2 ft. MGO - General Observation - MAG COAT 95% START74.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE131.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE313.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE392.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE392.2 ft. MGO - General Observation - MAG COAT 95% FINISH392.8 ft. AMH - Downstream Manhole, Survey Ends - 3:10AM

Observation photos (5)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

  • General Observation - MAG COAT 95% START

    2 ft. - General Observation - MAG COAT 95% START

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

    74.5 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

    131.9 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

    313.2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

Observations (11)

DistanceCodeObservation
392.8AMH3:10AM
74.5SSSBLISTERING PEELING CONCRETE
313.2SSSPEELING CONCRETE
0AMH2:45AM
2SSSBLISTERING PEELING CONCRETE UNDER MAG COAT
0MWL
0MWM
392.2SSSBLISTERING PEELING CONCRETE
131.9SSSPEELING CONCRETE
392.2MGOMAG COAT 95% FINISH
2MGOMAG COAT 95% START

Properties (6)

custom_field_three
BLISTERING PEELING CONCRETE- 95% MAG COAT
custom_field_two
3
customer
LACSD
datetime
2021-04-06T02:44:00-07:00
documentation
MARTIN,OLIVER 111,CASTILLO,RUVALCABA
is_lateral_inspection
false