Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 23, 2021, 06:40 AM
  • F 0227_F 0226_02222021_225257.mp4

Date
02/22/2021
W/O
875064
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00051
PipeID
P10357
Time
10:40 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8580
Sewer Name
F JOINT OUTFALL F - UNIT 7J
City
LA MIRADA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
36
Purpose
Routine Assessment
Project
RFIR_WO_875064_TV18079_FEB2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
78 in.
Upstream MH
F 0227
Downstream MH
F 0226
Dir. of Survey
Downstream
Length Surveyed
363.1 ft.
Total Length
363.1 ft.
Structural Index
3
Structural Quick
3M2M
Structural Rating
360
O&M Index
2
O&M Quick
2M00
O&M Rating
144
Overall Index
2
Overall Quick
Overall Rating
504
Pipe schematic from manhole F 0227 to F 0226
MH: F 0227MH: F 0226downstream0 ft. AMH - Upstream Manhole, Survey Begins - F 02270 ft. MGO - General Observation - ROACHES I@ MH0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. MGO - General Observation - 65% MAG COAT2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start230.2 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"325.5 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: YES, 6"361 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish361 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish361 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish363.1 ft. AMH - Downstream Manhole, Survey Ends - F 0226

Observation photos (2)

  • General Observation - ROACHES I@ MH

    0 ft. - General Observation - ROACHES I@ MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
0AMHF 0227
361DAGS
2MGO65% MAG COAT
0MGOROACHES I@ MH
363.1AMHF 0226
325.5TBA
2SSS
361SSS
230.2TBA
0MWM
2SAV
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
361SAV
2DAGS
0MWL

Properties (7)

additional_info
630069022221201
custom_field_three
VISIBLE AGGREGATE
custom_field_two
3
customer
1
datetime
2021-02-22T22:40:49-08:00
documentation
PRO PIPE
is_lateral_inspection
false