Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 15, 2021, 11:15 AM
  • 20 0126A_20 0126_02152021_024657.mp4

Date
02/15/2021
W/O
875307
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00744
PipeID
P19050
Time
3:15 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8569
Sewer Name
20 TRUNK "C"
City
PALMDALE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 20
Page No.
01
Purpose
Routine Assessment
Project
RFIR_WO_875307_TV20027_FEB2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
20 0126A
Downstream MH
20 0126
Dir. of Survey
Downstream
Length Surveyed
60.8 ft.
Total Length
60.8 ft.
Structural Index
3
Structural Quick
3A2A
Structural Rating
60
O&M Index
2
O&M Quick
312A
O&M Rating
27
Overall Index
2
Overall Quick
Overall Rating
87
Pipe schematic from manhole 20 0126A to 20 0126
MH: 20 0126AMH: 20 0126downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 20 0126A2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start43.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"47.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"59.6 ft. OBM - Obstacles Pipe Material, 20 %of cross sectional area, from 08 to 02 o'clock60.8 ft. MSA - Survey Abandoned - DUE TO OBSTRUCTION/PIPE MATERIAL.60.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish60.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish60.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (4)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Survey Abandoned - DUE TO OBSTRUCTION/PIPE MATERIAL.

    60.8 ft. - Survey Abandoned - DUE TO OBSTRUCTION/PIPE MATERIAL.

Observations (14)

DistanceCodeObservation
60.8MSADUE TO OBSTRUCTION/PIPE MATERIAL.
59.6OBM
0MWM
0MWL
2SAP
60.8SSS
0MGOCONNECTION AT MH 3 O'CLOCK
60.8SAP
0AMH20 0126A
2SSS
2DAGS
43.5TFC
47.6TFC
60.8DAGS

Properties (7)

additional_info
630069021521001
custom_field_three
ABANDONED DUE TO PIPE MATERIAL/OBSTRUCTION
custom_field_two
5
customer
1
datetime
2021-02-15T03:15:45-08:00
documentation
PRO PIPE
is_lateral_inspection
false