- Date
- 04/02/2021
- W/O
- 0880015
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00134
- PipeID
- P09767
- Time
- 1:10 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- H1764
- Sewer Name
- C JOINT OUTFALL C - UNIT 6E
- City
- ARTESIA
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 19
- Page No.
- 04
- Purpose
- Capital Improvement Program Assesment
- Project
- 20210402MDM_JOINT_OUTFALL_UNIT_6E
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 24 in.
- Upstream MH
- C 0307
- Downstream MH
- C 0306
- Dir. of Survey
- Downstream
- Length Surveyed
- 161.9 ft.
- Total Length
- 161.9 ft.
- Structural Index
- 2
- Structural Quick
- 2100
- Structural Rating
- 2
- O&M Index
- 2
- O&M Quick
- 322A
- O&M Rating
- 28
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 30
Pipe schematic from manhole C 0307 to C 0306 Observation photos (5)

2 ft. - General Observation - MAG COAT 98% START

2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

9 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

74 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 01 to 04 o'clock, , within 8 inches of joint: YES

161.5 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: NO - INSIDE MH