Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 3, 2021, 07:05 AM
  • B 0515_B 0514_03022021_231509.mp4

Date
03/02/2021
W/O
875022
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00099
PipeID
P09062
Time
11:05 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8627
Sewer Name
B JOINT OUTFALL B - UNIT 6E
City
ROSEMEAD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
27
Purpose
Routine Assessment
Project
WO_875022_TV15111_FEB2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
39 in.
Width
27 in.
Upstream MH
B 0515
Downstream MH
B 0514
Dir. of Survey
Downstream
Length Surveyed
442.2 ft.
Total Length
442.2 ft.
Structural Index
2
Structural Quick
2P00
Structural Rating
170
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
174
Pipe schematic from manhole B 0515 to B 0514
MH: B 0515MH: B 0514downstream0 ft. AMH - Upstream Manhole, Survey Begins - B 05150 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area13.2 ft. MGO - General Observation - MAG COAT13.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start35.5 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 8"94.5 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 8"246.1 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 8"437 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish442.2 ft. AMH - Downstream Manhole, Survey Ends - B 0514

Observation photos (4)

  • General Observation - MAG COAT

    13.2 ft. - General Observation - MAG COAT

  • Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 8"

    35.5 ft. - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 8"

  • Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 8"

    94.5 ft. - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 8"

  • Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 8"

    246.1 ft. - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 8"

Observations (10)

DistanceCodeObservation
35.5TB
246.1TB
13.5SSS
0AMHB 0515
94.5TBA
13.2MGOMAG COAT
437SSS
442.2AMHB 0514
0MWL
0MWM

Properties (6)

custom_field_three
SPALLING
custom_field_two
3
customer
1
datetime
2021-03-02T23:05:21-08:00
documentation
PRO PIPE
is_lateral_inspection
false