Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 22, 2021, 10:08 AM
  • 04 0071_04 0070_02222021_022319.mp4

Date
02/22/2021
W/O
875394
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00415
PipeID
P11807
Time
2:08 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8579
Sewer Name
04 SHERMAN TRUNK
City
WEST HOLLYWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 04
Page No.
03
Purpose
Capital Improvement Program Assesment
Project
RFIR_WO_875394_TV04009_FEB2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
04 0070
Downstream MH
04 0071
Dir. of Survey
Upstream
Length Surveyed
241 ft.
Total Length
241 ft.
Structural Index
3
Structural Quick
3H21
Structural Rating
143
O&M Index
2
O&M Quick
2Q11
O&M Rating
179
Overall Index
2
Overall Quick
Overall Rating
322
Pipe schematic from manhole 04 0070 to 04 0071
MH: 04 0070MH: 04 0071upstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Ends - 04 00712 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish15.4 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"30.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"32.8 ft. IW - Infiltration Weeper, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish72.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"73.6 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"93.1 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start109.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"133 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"133 ft. RFL - Roots Fine Lateral, from 07 to 11 o'clock147.2 ft. IW - Infiltration Weeper, from 09 to 03 o'clock, within 8 inches of joint: YES, Start147.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"180.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"187.5 ft. IW - Infiltration Weeper, at 10 o'clock, within 8 inches of joint: YES224.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"227.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start227.9 ft. H - Hole, at 12 o'clock, within 8 inches of joint: YES - POSSIBLE BREAK-IN CONNECTION228.1 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES230.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"230.8 ft. H - Hole, at 11 o'clock, within 8 inches of joint: YES - POSSIBLE BREAK-IN CONNECTION239 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start241 ft. AMH - Downstream Manhole, Survey Begins - 04 0070241 ft. MGO - General Observation - COCKROACHES IN MANHOLE241 ft. MWL - Water Level, 5 %of cross sectional area241 ft. MWM - Water Mark, 10 %of cross sectional area

Observation photos (11)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Hole, at 11 o'clock, within 8 inches of joint: YES - POSSIBLE BREAK-IN CONNECTION

    10.2 ft. - Hole, at 11 o'clock, within 8 inches of joint: YES - POSSIBLE BREAK-IN CONNECTION

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    12.9 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Hole, at 12 o'clock, within 8 inches of joint: YES - POSSIBLE BREAK-IN CONNECTION

    13.1 ft. - Hole, at 12 o'clock, within 8 inches of joint: YES - POSSIBLE BREAK-IN CONNECTION

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    13.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Infiltration Weeper, at 10 o'clock, within 8 inches of joint: YES

    53.5 ft. - Infiltration Weeper, at 10 o'clock, within 8 inches of joint: YES

  • Infiltration Weeper, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    93.8 ft. - Infiltration Weeper, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Lateral, from 07 to 11 o'clock

    108 ft. - Roots Fine Lateral, from 07 to 11 o'clock

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    147.9 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    241 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (29)

DistanceCodeObservation
108TFA
241MGOCOCKROACHES IN MANHOLE
241AMH04 0071
93.7TFA
239DAGS
60.7TFA
167.4TBA
225.6TFC
168.8TFA
0AMH04 0070
108RFL
10.2TFA
0MGOCOCKROACHES IN MANHOLE
13.6CM
10.2HPOSSIBLE BREAK-IN CONNECTION
0MWL
131.4TFA
210.3TFA
147.9DAE
239DAE
239CM
16.6TFA
13.1HPOSSIBLE BREAK-IN CONNECTION
93.8IW
53.5IW
2DAGS
208.2IW
0MWM
12.9CL

Properties (7)

additional_info
630069022221001
custom_field_three
MULTIPLE CRACKS
custom_field_two
2
customer
1
datetime
2021-02-22T02:08:08-08:00
documentation
PRO PIPE
is_lateral_inspection
false