Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 23, 2021, 05:41 AM
  • 05 0726_05 0725_02222021_221731.mp4

Date
02/22/2021
W/O
875313
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00521
PipeID
P05949
Time
9:41 PM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8524
Sewer Name
05 SOUTH INGLEWOOD-ORANGE AVENUE TRUNK, EXTENSION #1
City
INGLEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
07
Purpose
Routine Assessment
Project
RFIR_WO_875313_TV05333_FEB2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
05 0726
Downstream MH
05 0725
Dir. of Survey
Downstream
Length Surveyed
374.6 ft.
Total Length
374.6 ft.
Structural Index
4
Structural Quick
514N
Structural Rating
300
O&M Index
2
O&M Quick
2N1L
O&M Rating
213
Overall Index
2
Overall Quick
Overall Rating
513
Pipe schematic from manhole 05 0726 to 05 0725
MH: 05 0726MH: 05 0725downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 2 OC'LOCK0 ft. AMH - Upstream Manhole, Survey Begins - 05 07260 ft. MGO - General Observation - CONNECTION AT THE MH 4 OC'LOCK0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start3 ft. FL - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES4.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES11.4 ft. FH2 - Fracture Longitudinal Hinge, 2, from 09 to 04 o'clock, within 8 inches of joint: YES20.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start38.9 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES45 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start57.3 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish68.9 ft. RFJ - Roots Fine Joint, from 03 to 04 o'clock, within 8 inches of joint: YES74.7 ft. B - Broken, from 08 to 04 o'clock, within 8 inches of joint: YES80.6 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start97.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4" - ROOTS159.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"222.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"281.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"334.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"335.8 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 4"374.6 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish374.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish374.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish374.6 ft. AMH - Downstream Manhole, Survey Ends - 05 0725

Observation photos (11)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES

    3 ft. - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    4.9 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal Hinge, 2, from 09 to 04 o'clock, within 8 inches of joint: YES

    11.4 ft. - Fracture Longitudinal Hinge, 2, from 09 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    20.9 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES

    38.9 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    45 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 03 to 04 o'clock, within 8 inches of joint: YES

    68.9 ft. - Roots Fine Joint, from 03 to 04 o'clock, within 8 inches of joint: YES

  • Broken, from 08 to 04 o'clock, within 8 inches of joint: YES

    74.7 ft. - Broken, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    80.6 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4" - ROOTS

    97.3 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4" - ROOTS

Observations (26)

DistanceCodeObservation
0MWM
374.6RFJ
374.6DAGS
74.7B
97.3TFROOTS
0MGOCONNECTION AT THE MH 2 OC'LOCK
68.9RFJ
0AMH05 0726
80.6RFJ
3FL
334.7TFC
374.6FM
38.9RFJ
20.9FM
281.7TF
374.6AMH05 0725
335.8TB
0MGOCONNECTION AT THE MH 4 OC'LOCK
11.4FH2
57.3RFJ
4.9FM
2DAGS
222.2TFA
45RFJ
159.7TF
0MWL

Properties (7)

additional_info
630074022221201
custom_field_three
BROKEN PIPE/MULTIPLE FRACTURE
custom_field_two
1
customer
1
datetime
2021-02-22T21:41:44-08:00
documentation
PROPIPE
is_lateral_inspection
false