Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 23, 2021, 06:18 AM
  • 05 0725_05 0724_02222021_224847.mp4

Date
02/22/2021
W/O
875313
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00521
PipeID
P05948
Time
10:18 PM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8524
Sewer Name
05 SOUTH INGLEWOOD-ORANGE AVENUE TRUNK, EXTENSION #1
City
INGLEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
07
Purpose
Routine Assessment
Project
RFIR_WO_875313_TV05333_FEB2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
05 0725
Downstream MH
05 0724
Dir. of Survey
Downstream
Length Surveyed
352.7 ft.
Total Length
352.7 ft.
Structural Index
4
Structural Quick
524M
Structural Rating
316
O&M Index
2
O&M Quick
482M
O&M Rating
172
Overall Index
3
Overall Quick
Overall Rating
488
Pipe schematic from manhole 05 0725 to 05 0724
MH: 05 0725MH: 05 0724downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 07250 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start5.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start12.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"59.7 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 4"65.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"105.7 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 4"113.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"166.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"194.6 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 4"205.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"207.6 ft. B - Broken, from 08 to 04 o'clock, within 8 inches of joint: YES211.9 ft. B - Broken, from 09 to 03 o'clock, within 8 inches of joint: YES272.5 ft. MWLS - Water Level, Sag in pipe, 50 %of cross sectional area, Start284 ft. MCU - Camera Underwater, Start324.2 ft. MWLS - Water Level, Sag in pipe, 50 %of cross sectional area, Finish324.2 ft. MCU - Camera Underwater, Finish350 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish350 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish352.7 ft. AMH - Downstream Manhole, Survey Ends - 05 0724

Observation photos (3)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Broken, from 08 to 04 o'clock, within 8 inches of joint: YES

    207.6 ft. - Broken, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Broken, from 09 to 03 o'clock, within 8 inches of joint: YES

    211.9 ft. - Broken, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (23)

DistanceCodeObservation
2DAGS
59.7TB
5.2FM
352.7AMH05 0724
272.5MWLS
0AMH05 0725
0MWL
211.9B
0MWM
205.5TFC
65.9TFC
113.3TFC
12.5TF
324.2MWLS
194.6TB
350FM
207.6B
166.6TFC
350DAGS
324.2MCU
105.7TB
284MCU
0MGOCONNECTION AT THE MH 9 OC'LOCK

Properties (7)

additional_info
630074022221201
custom_field_three
BROKEN PIPE/MULTIPLE FRACTURE/SAG
custom_field_two
1
customer
1
datetime
2021-02-22T22:18:50-08:00
documentation
PROPIPE
is_lateral_inspection
false