Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 19, 2021, 05:49 AM
  • 01 1126_01 1125_02182021_220149.mp4

Date
02/18/2021
W/O
875676
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00210
PipeID
P01978
Time
9:49 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8577
Sewer Name
01 HUNTINGTON PARK TRUNK
City
HUNTINGTON PARK
Loc. details
Alley
Location Code
H
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
04
Purpose
Capital Improvement Program Assesment
Project
RFIR_WO_875676_TV01246_FEB2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
24 in.
Upstream MH
01 1126
Downstream MH
01 1125
Dir. of Survey
Downstream
Length Surveyed
280.7 ft.
Total Length
280.7 ft.
Structural Index
3
Structural Quick
3I00
Structural Rating
150
O&M Index
2
O&M Quick
2J00
O&M Rating
110
Overall Index
2
Overall Quick
Overall Rating
260
Pipe schematic from manhole 01 1126 to 01 1125
MH: 01 1126MH: 01 1125downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 01 11262 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start21.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"28.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start62.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"68 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"106.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"113.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"144.5 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"150 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"174.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"195.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"219.2 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"242.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"247.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"278.4 ft. MGO - General Observation - COCKROACHES IN MANHOLE278.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish278.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish280.7 ft. AMH - Downstream Manhole, Survey Ends - 01 1125

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    28.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    278.4 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (22)

DistanceCodeObservation
278.4MGOCOCKROACHES IN MANHOLE
174.9TFA
219.2TFA
0MWL
28.5CM
0MWM
278.4CM
247.2TFA
113.9TFA
195.5TFA
21.4TFA
242.1TFA
0MGOCOCKROACHES IN MANHOLE
280.7AMH01 1125
0AMH01 1126
68TFA
278.4DAGS
106.2TFA
144.5TBA
2DAGS
62.5TFA
150TF

Properties (7)

additional_info
630069021821201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-02-18T21:49:26-08:00
documentation
PRO PIPE
is_lateral_inspection
false