- Date
- 02/18/2021
- W/O
- 875676
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00210
- PipeID
- P01978
- Time
- 9:49 PM
- Certificate
- U-0720-70309212
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K8577
- Sewer Name
- 01 HUNTINGTON PARK TRUNK
- City
- HUNTINGTON PARK
- Loc. details
- Alley
- Location Code
- H
- Use of Sewer
- Sanitary Sewer
- District
- District 01
- Page No.
- 04
- Purpose
- Capital Improvement Program Assesment
- Project
- RFIR_WO_875676_TV01246_FEB2021
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 15 in.
- Width
- 24 in.
- Upstream MH
- 01 1126
- Downstream MH
- 01 1125
- Dir. of Survey
- Downstream
- Length Surveyed
- 280.7 ft.
- Total Length
- 280.7 ft.
- Structural Index
- 3
- Structural Quick
- 3I00
- Structural Rating
- 150
- O&M Index
- 2
- O&M Quick
- 2J00
- O&M Rating
- 110
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 260
Pipe schematic from manhole 01 1126 to 01 1125 Observation photos (4)

0 ft. - General Observation - COCKROACHES IN MANHOLE

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

28.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

278.4 ft. - General Observation - COCKROACHES IN MANHOLE