Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 19, 2021, 08:00 AM
  • 01 1082_01 1081_02192021_001247.mp4

Date
02/19/2021
W/O
875676
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00210
PipeID
P01931
Time
12:00 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8577
Sewer Name
01 HUNTINGTON PARK TRUNK
City
CUDAHY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
08
Purpose
Capital Improvement Program Assesment
Project
RFIR_WO_875676_TV01246_FEB2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
18 in.
Upstream MH
01 1082
Downstream MH
01 1081
Dir. of Survey
Downstream
Length Surveyed
395.1 ft.
Total Length
395.1 ft.
Structural Index
3
Structural Quick
413J
Structural Rating
199
O&M Index
2
O&M Quick
2R00
O&M Rating
192
Overall Index
2
Overall Quick
Overall Rating
391
Pipe schematic from manhole 01 1082 to 01 1081
MH: 01 1082MH: 01 1081downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 10820 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start40.2 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start92.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES129.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start129.2 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish301.2 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS391 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish392.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish392.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish395.1 ft. AMH - Downstream Manhole, Survey Ends - 01 1081395.1 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (6)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    40.2 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    92.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    129.2 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    395.1 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (15)

DistanceCodeObservation
392.7DAGS
92.6FM
392.7FL
0AMH01 1082
0MWL
0MGOCOCKROACHES IN MANHOLE
2DAGS
395.1AMH01 1081
301.2DSZDEBRIS
395.1MGOCOCKROACHES IN MANHOLE
129.2FL
129.2CL
40.2CL
391DSZ
0MWM

Properties (7)

additional_info
630069021821201
custom_field_three
FRACTURES/CRACKS
custom_field_two
2
customer
1
datetime
2021-02-19T00:00:44-08:00
documentation
PRO PIPE
is_lateral_inspection
false