Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 22, 2021, 12:18 PM
  • C 0390_C 0389_02222021_043039.mp4

Date
02/22/2021
W/O
875033
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00142
PipeID
P09854
Time
4:18 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8615
Sewer Name
C JOINT OUTFALL C - UNIT 8D
City
CERRITOS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
04
Purpose
Capital Improvement Program Assesment
Project
RFIR_WO_875033_TV19055_FEB2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Width
114 in.
Upstream MH
C 0390
Downstream MH
C 0389
Dir. of Survey
Downstream
Length Surveyed
343.2 ft.
Total Length
343.2 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2[00
O&M Rating
278
Overall Index
2
Overall Quick
Overall Rating
278
Pipe schematic from manhole C 0390 to C 0389
MH: C 0390MH: C 0389downstream0 ft. AMH - Upstream Manhole, Survey Begins - C 03900 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start4.4 ft. DSC - Deposits Settled Compacted, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start33.6 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 10 o'clock, , within 8 inches of joint: YES51.1 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 12 to 02 o'clock, , within 8 inches of joint: YES332.5 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES343.2 ft. DSC - Deposits Settled Compacted, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Finish343.2 ft. AMH - Downstream Manhole, Survey Ends - C 0389343.2 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK343.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Settled Compacted,  5 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: YES, Start

    4.4 ft. - Deposits Settled Compacted, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 10 o'clock,  , within 8 inches of joint: YES

    33.6 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 10 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 12 to 02 o'clock,  , within 8 inches of joint: YES

    51.1 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 12 to 02 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    332.5 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

Observations (12)

DistanceCodeObservation
343.2DSC
0AMHC 0390
343.2AMHC 0389
0MWM
2.5DAGS
51.1DAE
343.2MGOCONNECTION AT MH, 3 O'CLOCK
33.6DAE
0MWL
343.2DAGS
4.4DSC
332.5DAE

Properties (7)

custom_field_three
GREASE, DEBRIS
custom_field_two
3
customer
1
datetime
2021-02-22T04:18:52-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
26643