Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 22, 2021, 12:31 PM
  • C 0389_C 0388_02222021_045247.mp4

Date
02/22/2021
W/O
875033
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00142
PipeID
P09853
Time
4:31 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8615
Sewer Name
C JOINT OUTFALL C - UNIT 8D
City
CERRITOS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
04
Purpose
Capital Improvement Program Assesment
Project
RFIR_WO_875033_TV19055_FEB2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Width
114 in.
Upstream MH
C 0389
Downstream MH
C 0388
Dir. of Survey
Downstream
Length Surveyed
351.9 ft.
Total Length
351.9 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
312Z
O&M Rating
277
Overall Index
2
Overall Quick
Overall Rating
277
Pipe schematic from manhole C 0389 to C 0388
MH: C 0389MH: C 0388downstream0 ft. AMH - Upstream Manhole, Survey Begins - C 03890 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK0 ft. MWM - Water Mark, 35 %of cross sectional area2.4 ft. ID - Infiltration Dripper, at 01 o'clock, within 8 inches of joint: YES2.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.4 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 12 to 04 o'clock, , within 8 inches of joint: YES42.2 ft. DSC - Deposits Settled Compacted, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start203.6 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES309.6 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES323.5 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 10 o'clock, , within 8 inches of joint: YES328.7 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 12 o'clock, , within 8 inches of joint: YES351.9 ft. MGO - General Observation - INFILTRAION AT CONNECTION351.9 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK351.9 ft. AMH - Downstream Manhole, Survey Ends - C 0388351.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish351.9 ft. DSC - Deposits Settled Compacted, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Finish351.9 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK

Observation photos (9)

  • Infiltration Dripper, at 01 o'clock, within 8 inches of joint: YES

    2.4 ft. - Infiltration Dripper, at 01 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 10 %of cross sectional area, from 12 to 04 o'clock,  , within 8 inches of joint: YES

    2.4 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, from 12 to 04 o'clock, , within 8 inches of joint: YES

  • Deposits Settled Compacted,  5 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: YES, Start

    42.2 ft. - Deposits Settled Compacted, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    203.6 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    309.6 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 10 o'clock,  , within 8 inches of joint: YES

    323.5 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 10 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 12 o'clock,  , within 8 inches of joint: YES

    328.7 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 12 o'clock, , within 8 inches of joint: YES

  • General Observation - INFILTRAION AT CONNECTION

    351.9 ft. - General Observation - INFILTRAION AT CONNECTION

Observations (18)

DistanceCodeObservation
309.6DAE
0AMHC 0389
203.6DAE
351.9MGOINFILTRAION AT CONNECTION
2.4ID
351.9MGOCONNECTION AT MH, 3 O'CLOCK
2.4DAGS
42.2DSC
351.9AMHC 0388
351.9DAGS
351.9DSC
323.5DAE
2.4DAE
0MWL
0MGOCONNECTION AT MH, 3 O'CLOCK
0MWM
328.7DAE
351.9MGOCONNECTION AT MH, 9 O'CLOCK

Properties (7)

custom_field_three
GREASE, DEBRIS INFILTRATION
custom_field_two
3
customer
1
datetime
2021-02-22T04:31:27-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
26643