Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 17, 2021, 09:16 AM
  • H 0108_H 0107_02172021_013429.mp4

Date
02/17/2021
W/O
875062
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00165
PipeID
P10559
Time
1:16 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8573
Sewer Name
H JOINT OUTFALL H - UNIT 1F
City
HUNTINGTON PARK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_875062_TV01242_FEB2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
H 0108
Downstream MH
H 0107
Dir. of Survey
Downstream
Length Surveyed
119.1 ft.
Total Length
119.1 ft.
Structural Index
3
Structural Quick
5C3D
Structural Rating
215
O&M Index
2
O&M Quick
412D
O&M Rating
50
Overall Index
3
Overall Quick
Overall Rating
265
Pipe schematic from manhole H 0108 to H 0107
MH: H 0108MH: H 0107downstream0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 01080 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start0 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. MGO - General Observation - 65% MAG COAT2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start117.2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish117.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish117.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish117.2 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish119.1 ft. MGO - General Observation - STOP LOG DOWN @ MH 3 O'CLOCK119.1 ft. AMH - Downstream Manhole, Survey Ends - H 0107

Observation photos (4)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    0 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
2MGO65% MAG COAT
2DAGS
0MWL
117.2SAP
0AMHH 0108
117.2DAGS
119.1MGOSTOP LOG DOWN @ MH 3 O'CLOCK
119.1AMHH 0107
0SSS
2SAP
117.2SSS
0MWM
2SRV
117.2SRV

Properties (7)

additional_info
630069021621201
custom_field_three
VISIBLE REINFORCEMENT/PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2021-02-17T01:16:48-08:00
documentation
PRO PIPE
is_lateral_inspection
false