Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 18, 2021, 10:13 AM
  • 01 1355_01 0799_02182021_023026.mp4

Date
02/18/2021
W/O
875316
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00197
PipeID
P01503
Time
2:13 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8576
Sewer Name
01 BULLIS ROAD-TEMPLE STREET TRUNK
City
LYNWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_875316_TV01264_FEB2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
36 in.
Upstream MH
01 1355
Downstream MH
01 0799
Dir. of Survey
Downstream
Length Surveyed
325.9 ft.
Total Length
325.9 ft.
Structural Index
4
Structural Quick
4K25
Structural Rating
246
O&M Index
2
O&M Quick
412L
O&M Rating
132
Overall Index
3
Overall Quick
Overall Rating
378
Pipe schematic from manhole 01 1355 to 01 0799
MH: 01 1355MH: 01 0799downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 01 13550 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start26.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start26.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish50.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"69.1 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"74.4 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"95.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"116.9 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"121.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"149.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"164 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"173.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"197.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"209 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"217.8 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"244.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"256.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"286.8 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"295.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"322.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish322.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish324.9 ft. MGO - General Observation - COCKROACHES IN MANHOLE325.9 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK325.9 ft. AMH - Downstream Manhole, Survey Ends - 01 0799

Observation photos (4)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    26.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    324.9 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (29)

DistanceCodeObservation
2CL
209TFC
322.7DAGS
164TFA
116.9TFC
2DAGS
295.3TFC
244.9TFC
0MWL
149.1TFC
324.9MGOCOCKROACHES IN MANHOLE
95.6TFC
197.5TFC
325.9MGOCONNECTION AT MH 3 O'CLOCK
69.1TFC
322.7FM
217.8TFC
173.4TFC
74.4TFC
0MGOCOCKROACHES IN MANHOLE
121.9TFC
50.8TFC
26.7FM
325.9AMH01 0799
286.8TFC
0AMH01 1355
26.7CL
256.6TFC
0MWM

Properties (7)

additional_info
630069021721203
custom_field_three
MULTIPLE FRACTURES
custom_field_two
2
customer
1
datetime
2021-02-18T02:13:38-08:00
documentation
PRO PIPE
is_lateral_inspection
false