Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 18, 2021, 09:15 AM
  • 01 1369_01 0795_02182021_012205.mp4

Date
02/18/2021
W/O
875316
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00197
PipeID
P01498
Time
1:15 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8576
Sewer Name
01 BULLIS ROAD-TEMPLE STREET TRUNK
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_875316_TV01264_FEB2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
36 in.
Upstream MH
01 1369
Downstream MH
01 0795
Dir. of Survey
Downstream
Length Surveyed
134.2 ft.
Total Length
134.2 ft.
Structural Index
3
Structural Quick
3D00
Structural Rating
78
O&M Index
2
O&M Quick
412D
O&M Rating
56
Overall Index
3
Overall Quick
Overall Rating
134
Pipe schematic from manhole 01 1369 to 01 0795
MH: 01 1369MH: 01 0795downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 13692 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start8.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"56.8 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"80.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"108 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"128.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"132.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish132.6 ft. MGO - General Observation - COCKROACHES IN MANHOLE132.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish134.2 ft. AMH - Downstream Manhole, Survey Ends - 01 0795

Observation photos (3)

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    132.6 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (14)

DistanceCodeObservation
2FL
2DAGS
108TFC
56.8TF
0MWL
8.6TFC
132.6FL
0MWM
80.8TFC
128.7TFC
132.6MGOCOCKROACHES IN MANHOLE
134.2AMH01 0795
132.6DAGS
0AMH01 1369

Properties (7)

additional_info
630069021721203
custom_field_three
CONTINUOUS LONGITUDINAL FRACTURE
custom_field_two
2
customer
1
datetime
2021-02-18T01:15:46-08:00
documentation
PRO PIPE
is_lateral_inspection
false