Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 18, 2021, 09:34 AM
  • 01 0794_01 0793_02182021_014900.mp4

Date
02/18/2021
W/O
875316
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00197
PipeID
P01496
Time
1:34 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8576
Sewer Name
01 BULLIS ROAD-TEMPLE STREET TRUNK
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_875316_TV01264_FEB2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
36 in.
Upstream MH
01 0794
Downstream MH
01 0793
Dir. of Survey
Downstream
Length Surveyed
294.9 ft.
Total Length
294.9 ft.
Structural Index
4
Structural Quick
4K00
Structural Rating
232
O&M Index
2
O&M Quick
412K
O&M Rating
120
Overall Index
3
Overall Quick
Overall Rating
352
Pipe schematic from manhole 01 0794 to 01 0793
MH: 01 0794MH: 01 0793downstream0 ft. MWM - Water Mark, 60 %of cross sectional area0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 07940 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MGO - General Observation - COCKROACHES IN MANHOLE2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start3.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start13.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"65.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"76.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"113.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"134.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"164.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"182.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"215.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"234 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"267.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"282.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"292.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish292.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish294.9 ft. MGO - General Observation - COCKROACHES IN MANHOLE294.9 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK294.9 ft. AMH - Downstream Manhole, Survey Ends - 01 0793

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.5 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    294.9 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (23)

DistanceCodeObservation
292.7FM
0MWM
215.8TFC
182.6TFC
0MWL
134.6TFC
2DAGS
76.6TFC
267.9TFC
292.7DAGS
282.6TFC
3.5FM
234TFC
0AMH01 0794
113.5TFC
294.9MGOCOCKROACHES IN MANHOLE
0MGOCONNECTION AT MH 3 O'CLOCK
13.9TFC
294.9MGOCONNECTION AT MH 9 O'CLOCK
164.8TFC
294.9AMH01 0793
0MGOCOCKROACHES IN MANHOLE
65.6TFC

Properties (7)

additional_info
630069021721203
custom_field_three
MULTIPLE FRACTURES
custom_field_two
2
customer
1
datetime
2021-02-18T01:34:47-08:00
documentation
PRO PIPE
is_lateral_inspection
false