Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 25, 2021, 08:39 AM
  • 08 0001_08 0000_3252021_021243.mp4

Date
03/25/2021
W/O
0875140
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00561
PipeID
P21471
Time
1:39 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1758
Sewer Name
08 MAIN STREET P.P. INFLUENT SEWER
City
CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Capital Improvement Program Assesment
Project
20210325MDM_MAIN_STREET_P_P_INFLUENT_SEWER
Material
CIP
Shape
Circular
Height
30 in.
Upstream MH
08 0001
Downstream MH
08 0000
Dir. of Survey
Downstream
Length Surveyed
2.5 ft.
Total Length
2.5 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
5
O&M Quick
5541
O&M Rating
29
Overall Index
5
Overall Quick
Overall Rating
32
Pipe schematic from manhole 08 0001 to 08 0000
MH: 08 0001MH: 08 0000downstream0 ft. MWL - Water Level, 50 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:55AM0 ft. MGP - General Photograph - 60%2 ft. DSZ - Deposits Settled Other, 60 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: NO - BROKEN PIPE APPOX 3' DOWMSTREAM2 ft. DSZ - Deposits Settled Other, 60 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: NO - BROKEN CLAY PIPE2 ft. SCP - Surface Corrosion Metal Pipe, from 09 to 03 o'clock, within 8 inches of joint: YES, Change2 ft. DSZ - Deposits Settled Other, 60 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: NO - BROKEN CLAY PIPE2 ft. DSZ - Deposits Settled Other, 60 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: NO - BROKEN CLAY PIPE2 ft. DSZ - Deposits Settled Other, 60 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: NO - BROKEN CLAY PIPE2.5 ft. MSA - Survey Abandoned - 60% TO 70% BROKEN PIPE AT MH OPENING

Observation photos (6)

  • Deposits Settled Other,  60 %of cross sectional area, from 02 to 10 o'clock,  , within 8 inches of joint: NO - BROKEN PIPE APPOX 3' DOWMSTREAM

    2 ft. - Deposits Settled Other, 60 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: NO - BROKEN PIPE APPOX 3' DOWMSTREAM

  • Deposits Settled Other,  60 %of cross sectional area, from 02 to 10 o'clock,  , within 8 inches of joint: NO - BROKEN CLAY PIPE

    2 ft. - Deposits Settled Other, 60 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: NO - BROKEN CLAY PIPE

  • Surface Corrosion Metal Pipe, from 09 to 03 o'clock, within 8 inches of joint: YES, Change

    2 ft. - Surface Corrosion Metal Pipe, from 09 to 03 o'clock, within 8 inches of joint: YES, Change

  • Deposits Settled Other,  60 %of cross sectional area, from 02 to 10 o'clock,  , within 8 inches of joint: NO - BROKEN CLAY PIPE

    2 ft. - Deposits Settled Other, 60 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: NO - BROKEN CLAY PIPE

  • Deposits Settled Other,  60 %of cross sectional area, from 02 to 10 o'clock,  , within 8 inches of joint: NO - BROKEN CLAY PIPE

    2 ft. - Deposits Settled Other, 60 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: NO - BROKEN CLAY PIPE

  • Deposits Settled Other,  60 %of cross sectional area, from 02 to 10 o'clock,  , within 8 inches of joint: NO - BROKEN CLAY PIPE

    2 ft. - Deposits Settled Other, 60 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: NO - BROKEN CLAY PIPE

Observations (11)

DistanceCodeObservation
0MWL
0MWM
2DSZBROKEN PIPE APPOX 3' DOWMSTREAM
2DSZBROKEN CLAY PIPE
2SCP
2DSZBROKEN CLAY PIPE
2DSZBROKEN CLAY PIPE
2.5MSA60% TO 70% BROKEN PIPE AT MH OPENING
0AMH1:55AM
0MGP60%
2DSZBROKEN CLAY PIPE

Properties (4)

customer
LACSD
datetime
2021-03-25T01:39:25-07:00
documentation
MARTIN,OLIVER 111,CASTILLO,RUVALCABA
is_lateral_inspection
false