Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 23, 2021, 07:38 AM
  • B 0308_B 0307_02222021_235217.mp4

Date
02/22/2021
W/O
875025
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00086
PipeID
P08819
Time
11:38 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8616
Sewer Name
B JOINT OUTFALL B - UNIT 3A
City
ROSEMEAD
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
21
Purpose
Routine Assessment
Project
WO_875025_TV15103_FEB2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Width
24 in.
Upstream MH
B 0308
Downstream MH
B 0307
Dir. of Survey
Downstream
Length Surveyed
322.6 ft.
Total Length
322.6 ft.
Structural Index
2
Structural Quick
2L00
Structural Rating
128
O&M Index
2
O&M Quick
2L00
O&M Rating
128
Overall Index
2
Overall Quick
Overall Rating
256
Pipe schematic from manhole B 0308 to B 0307
MH: B 0308MH: B 0307downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/UNKNOWN0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. MGO - General Observation - ROACHES @ MH0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 03082 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - 60% MAG COAT320 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish320.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish322.6 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE322.6 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/OPEN322.6 ft. AMH - Downstream Manhole, Survey Ends - B 0307

Observation photos (2)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - 60% MAG COAT

    2 ft. - General Observation - 60% MAG COAT

Observations (14)

DistanceCodeObservation
0MWM
0MGOCONN @ MH 3 O'CLOCK/UNKNOWN
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
322.6MGOCONN @ MH 9 O'CLOCK/ACTIVE
0MGOROACHES @ MH
0MWL
320DAGS
0AMHB 0308
2DAGS
320.1SSS
2SSS
322.6MGOCONN @ MH 3 O'CLOCK/OPEN
2MGO60% MAG COAT
322.6AMHB 0307

Properties (6)

custom_field_three
MAG COAT, SPALLING
custom_field_two
3
customer
1
datetime
2021-02-22T23:38:52-08:00
documentation
PRO PIPE
is_lateral_inspection
false