Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 30, 2020, 09:03 AM
  • C 0397_C 0396_12302020_011528.mp4

Date
12/30/2020
W/O
865141
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00143
PipeID
P09865
Time
1:03 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8296
Sewer Name
C JOINT OUTFALL C - UNIT 8E
City
ARTESIA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
04
Purpose
Routine Assessment
Project
WO_865141_TV02139_DEC2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
114 in.
Upstream MH
C 0397
Downstream MH
C 0396
Dir. of Survey
Downstream
Length Surveyed
351.6 ft.
Total Length
351.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2M00
O&M Rating
140
Overall Index
2
Overall Quick
Overall Rating
140
Pipe schematic from manhole C 0397 to C 0396
MH: C 0397MH: C 0396downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - C 03970 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start37 ft. MGO - General Observation - POSSIBLE HANGING (1") JOINT SEAL @ 10 O'CLOCK141 ft. MGO - General Observation - POSSIBLE PROTRUDING JOINT SEAL FROM 11 TO 12 O'CLOCK154 ft. MGO - General Observation - JOINT SEAL HANGING APPROX. 1" @ 10 O'CLOCK230.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"243 ft. MGO - General Observation - POSSIBLE HANGING (1") JOINT SEAL @ 1 O'CLOCK260.1 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"337 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"349.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish351.6 ft. AMH - Downstream Manhole, Survey Ends - C 0396

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
37MGOPOSSIBLE HANGING (1") JOINT SEAL @ 10 O'CLOCK
2DAGS
0MWL
351.6AMHC 0396
0AMHC 0397
154MGOJOINT SEAL HANGING APPROX. 1" @ 10 O'CLOCK
337TFA
0MWM
243MGOPOSSIBLE HANGING (1") JOINT SEAL @ 1 O'CLOCK
349.6DAGS
141MGOPOSSIBLE PROTRUDING JOINT SEAL FROM 11 TO 12 O'CLOCK
230.8TFA
260.1TBA

Properties (8)

additional_info
630069122920202
custom_field_three
LIGHT GREASE
custom_field_two
4
customer
1
datetime
2020-12-30T01:03:11-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
26597