Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 30, 2020, 06:19 AM
  • C 0396_C 0395_12292020_223802.mp4

Date
12/29/2020
W/O
865141
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00143
PipeID
P09864
Time
10:19 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8296
Sewer Name
C JOINT OUTFALL C - UNIT 8E
City
ARTESIA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
04
Purpose
Routine Assessment
Project
WO_865141_TV02139_DEC2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
114 in.
Upstream MH
C 0396
Downstream MH
C 0395
Dir. of Survey
Downstream
Length Surveyed
400.7 ft.
Total Length
400.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2O00
O&M Rating
158
Overall Index
2
Overall Quick
Overall Rating
158
Pipe schematic from manhole C 0396 to C 0395
MH: C 0396MH: C 0395downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - C 03960 ft. MWM - Water Mark, 35 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start9.6 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"111.8 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"130.2 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"148 ft. MGO - General Observation - POSSIBLE HANGING (1") JOINT SEAL @ 10 O'CLOCK196 ft. MGO - General Observation - POSSIBLE HANGING (2") JOINT SEAL @ 11 O'CLOCK214 ft. MGO - General Observation - POSSIBLE HANGING (1") JOINT SEAL @ 3 O'CLOCK311.2 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"388 ft. MGO - General Observation - POSSIBLE PROTRUDING JOINT SEAL @ 11 O'CLOCK399.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish400.7 ft. AMH - Downstream Manhole, Survey Ends - C 0395

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
111.8TBA
0MWL
214MGOPOSSIBLE HANGING (1") JOINT SEAL @ 3 O'CLOCK
9.6TBA
2DAGS
388MGOPOSSIBLE PROTRUDING JOINT SEAL @ 11 O'CLOCK
196MGOPOSSIBLE HANGING (2") JOINT SEAL @ 11 O'CLOCK
0AMHC 0396
311.2TBA
130.2TBA
148MGOPOSSIBLE HANGING (1") JOINT SEAL @ 10 O'CLOCK
0MWM
399.1DAGS
400.7AMHC 0395

Properties (8)

additional_info
630069122920202
custom_field_three
LIGHT GREASE
custom_field_two
4
customer
1
datetime
2020-12-29T22:19:24-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
26597