- Date
- 02/12/2021
- W/O
- 875041
- Weather
- Light Rain
- Operator/Surveyor
- B.FUGATE
- Sewer ID
- Z00157
- PipeID
- P10047
- Time
- 2:40 AM
- Certificate
- U-508-7069
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K8480
- Sewer Name
- D JOINT OUTFALL D - UNIT 6 RELIEF
- City
- REDONDO BEACH
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 05
- Page No.
- 16
- Purpose
- Routine Assessment
- Project
- WO_875041_TV05145_FEB2021
- Sewer Type
- Gravity
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 39 in.
- Width
- 24 in.
- Upstream MH
- D 0171
- Downstream MH
- D 0170
- Dir. of Survey
- Downstream
- Length Surveyed
- 601.3 ft.
- Total Length
- 601.3 ft.
- Structural Index
- 3
- Structural Quick
- 513W
- Structural Rating
- 371
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 371
Pipe schematic from manhole D 0171 to D 0170 Observation photos (5)

6.9 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

7.5 ft. - Surface Reinforcement Visible, from 09 to 02 o'clock, within 8 inches of joint: YES

7.5 ft. - Surface Aggregate Projecting, from 07 to 01 o'clock, within 8 inches of joint: NO

165.1 ft. - Surface Aggregate Projecting, from 07 to 10 o'clock, within 8 inches of joint: NO

379.2 ft. - Surface Aggregate Projecting, from 12 to 02 o'clock, within 8 inches of joint: NO