Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 16, 2021, 10:08 AM
  • D 0159_A 1042_02162021_021508.mp4

Date
02/16/2021
W/O
875041
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00157
PipeID
P10036
Time
2:08 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8484
Sewer Name
D JOINT OUTFALL D - UNIT 6 RELIEF
City
LAWNDALE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
17
Purpose
Routine Assessment
Project
WO_875041_TV05145_FEB2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
39 in.
Width
27 in.
Upstream MH
D 0159
Downstream MH
A 1042
Dir. of Survey
Downstream
Length Surveyed
17.6 ft.
Total Length
17.6 ft.
Structural Index
4
Structural Quick
5133
Structural Rating
14
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
14
Pipe schematic from manhole D 0159 to A 1042
MH: D 0159MH: A 1042downstream0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - D 01590 ft. MGO - General Observation - CONNECTION AT THE MH 6 OC'LOCK2.1 ft. MGO - General Observation - MAG COAT2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start12.2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start17.6 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish17.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish17.6 ft. MGO - General Observation - CONNECTION AT THE MH 12 OC'LOCK17.6 ft. AMH - Downstream Manhole, Survey Ends - A 1042

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    12.2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

Observations (12)

DistanceCodeObservation
2.1MGOMAG COAT
0MGOCONNECTION AT THE MH 9 OC'LOCK
17.6SRV
2.1SAP
12.2SRV
17.6SAP
17.6MGOCONNECTION AT THE MH 12 OC'LOCK
0MWL
17.6AMHA 1042
0MWM
0AMHD 0159
0MGOCONNECTION AT THE MH 6 OC'LOCK

Properties (8)

additional_info
630074021521201
custom_field_three
AGGREGATE PROJECTING/REINFORCEMENT VISIBLE
custom_field_two
2
customer
1
datetime
2021-02-16T02:08:41-08:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
29986