Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 4, 2019, 11:31 AM
  • Section#8_18 1042_18 1041__242019__I0117.mp4

Date
02/04/2019
W/O
0753894
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00678
PipeID
P14896
Time
3:31 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0117
Sewer Name
18 LA HABRA HEIGHTS TRUNK, SECTION 2A
City
WHITTIER
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Capital Improvement Program Assesment
Project
20190201MDM_LA_HABRA_HEIGHTS_TRUNK_SECTION_2
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
18 1041
Downstream MH
18 1042
Dir. of Survey
Upstream
Length Surveyed
224.3 ft.
Total Length
224.3 ft.
Structural Index
2
Structural Quick
392A
Structural Rating
51
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
51
Pipe schematic from manhole 18 1041 to 18 1042
MH: 18 1041MH: 18 1042upstream0 ft. AMH - Downstream Manhole, Survey Ends - 4:15AM13.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, - SL38.2 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - SL41.2 ft. FL - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES, - SL41.2 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - SL44.2 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL52.3 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H68.1 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL72.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN90.4 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - SL98.5 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - HAIRLINE98.5 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - SL99.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN101 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - SL116.7 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - SL116.7 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL129.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN129.5 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - SL143.1 ft. MGO - General Observation - 10" VCP147.4 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - SL147.4 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SL152.3 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES - SL152.3 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - SL160.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN169.8 ft. FC - Fracture Circumferential, from 08 to 01 o'clock, within 8 inches of joint: YES - SL206.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN212 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL212.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN212.9 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SLIGHT224.3 ft. MWM - Water Mark, 30 %of cross sectional area224.3 ft. AMH - Upstream Manhole, Survey Begins - 3:40AM224.3 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (3)

  • General Observation - 10" VCP

    81.2 ft. - General Observation - 10" VCP

  • Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES,  - SL

    183.1 ft. - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES, - SL

  • Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - SL

    183.1 ft. - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - SL

Observations (32)

DistanceCodeObservation
172FCH
125.8FCHAIRLINE
210.8FLSL
107.6FCSL
224.3AMH4:15AM
17.6TFOPEN
151.6TFOPEN
156.2FCSL
125.2TFOPEN
81.2MGO10" VCP
186.1FLSL
0MWM
183.1FLSL
94.8TFOPEN
64.1TFOPEN
133.9FLSL
0AMH3:40AM
12.3FCSL
76.9FCSL
72FLSL
94.8FLSL
123.3FLSL
72FLSL
11.4TFOPEN
125.8FCSL
180.1FCSL
107.6FCSL
54.5FCSL
183.1FLSL
0MWL
76.9FCSL
11.4FCSLIGHT

Properties (6)

custom_field_three
SLIGHT FRACTURE JOINT TO JOINT
custom_field_two
2
customer
LACSD
datetime
2019-02-04T03:31:41-08:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false