Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 2, 2016, 08:24 AM
Date
05/02/2016
W/O
0563839
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00016
PipeID
P24998
Time
1:24 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6698
Sewer Name
08 MAIN STREET TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
07
Purpose
Capital Improvement Program Assesment
Project
20160430MDM_MAIN_STREET_TRUNK
Material
RCP-CTL
Shape
Circular
Height
33 in.
Upstream MH
08 0002
Downstream MH
08 0683
Dir. of Survey
Downstream
Length Surveyed
268.9 ft.
Total Length
268.9 ft.
Structural Index
4
Structural Quick
5G4J
Structural Rating
420
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
424
Pipe schematic from manhole 08 0002 to 08 0683
MH: 08 0002MH: 08 0683downstream0 ft. MGO - General Observation - MH CONN ACTIVE 3:000 ft. AMH - Upstream Manhole, Survey Begins - 4:20AM0 ft. MWM - Water Mark, 70 %of cross sectional area0 ft. MWL - Water Level, 50 %of cross sectional area0 ft. MGO - General Observation - MH CONN ACTIVE 9:002 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES - SEVERE AGG AREAS OF MISSING TILES2 ft. MGO - General Observation - MISSING TILES 80% START 10:00 TO 2:0015.2 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG17.4 ft. SRV - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: YES - CIRCUM24.1 ft. SRV - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR29.9 ft. SRV - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: YES - CIRCUM32.4 ft. SRV - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: YES - CIRCUM38.1 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR47.6 ft. SRC - Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: YES - CIRCUM59.8 ft. MGO - General Observation - MISSING TILES 60% START59.8 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - LONG CIRCUM REBAR73.9 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - LONG CICRUM REBAR111.4 ft. SRC - Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM117.6 ft. SRC - Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: YES, Finish129.3 ft. MGO - General Observation - MISSING TILES 30%140.5 ft. MGO - General Observation - MISSING TILES 80% START142.5 ft. SRV - Surface Reinforcement Visible, from 12 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM SPORATIC160 ft. SRV - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: YES - LONG CIRCUM REBAR174.9 ft. SRC - Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: YES - CIRCUM REBAR186.8 ft. SRC - Surface Reinforcement Corroded, from 11 to 02 o'clock, within 8 inches of joint: YES - LONG CIRCUM REBAR235.5 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO - LONG REBAR268.5 ft. SRV - Surface Reinforcement Visible, from 12 to 02 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR268.5 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG268.5 ft. MGO - General Observation - MISSING TILES 80% FINISH268.9 ft. AMH - Downstream Manhole, Survey Ends - 4:50AM

Observation photos (19)

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES - SEVERE AGG AREAS OF MISSING TILES

    2 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES - SEVERE AGG AREAS OF MISSING TILES

  • General Observation - MISSING TILES 80% START 10:00 TO 2:00

    2 ft. - General Observation - MISSING TILES 80% START 10:00 TO 2:00

  • Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

    15.2 ft. - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: YES - CIRCUM

    17.4 ft. - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: YES - CIRCUM

  • Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    24.1 ft. - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: YES - CIRCUM

    29.9 ft. - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: YES - CIRCUM

  • Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: YES - CIRCUM

    32.4 ft. - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: YES - CIRCUM

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

    38.1 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

  • Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: YES - CIRCUM

    47.6 ft. - Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: YES - CIRCUM

  • General Observation - MISSING TILES 60% START

    59.8 ft. - General Observation - MISSING TILES 60% START

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - LONG CICRUM REBAR

    73.9 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - LONG CICRUM REBAR

  • Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM

    111.4 ft. - Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM

  • General Observation - MISSING TILES 30%

    129.3 ft. - General Observation - MISSING TILES 30%

  • General Observation - MISSING TILES 80% START

    140.5 ft. - General Observation - MISSING TILES 80% START

  • Surface Reinforcement Visible, from 12 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM SPORATIC

    142.5 ft. - Surface Reinforcement Visible, from 12 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM SPORATIC

  • Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: YES - LONG CIRCUM REBAR

    160 ft. - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: YES - LONG CIRCUM REBAR

  • Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    174.9 ft. - Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 11 to 02 o'clock, within 8 inches of joint: YES - LONG CIRCUM REBAR

    186.8 ft. - Surface Reinforcement Corroded, from 11 to 02 o'clock, within 8 inches of joint: YES - LONG CIRCUM REBAR

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO - LONG REBAR

    235.5 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO - LONG REBAR

Observations (30)

DistanceCodeObservation
0MGOMH CONN ACTIVE 3:00
0AMH4:20AM
17.4SRVCIRCUM
129.3MGOMISSING TILES 30%
111.4SRCCIRCUM
174.9SRCCIRCUM REBAR
2SAMSEVERE AGG AREAS OF MISSING TILES
47.6SRCCIRCUM
142.5SRVCIRCUM SPORATIC
140.5MGOMISSING TILES 80% START
59.8MGOMISSING TILES 60% START
15.2SAVSEVERE AGG
24.1SRVCIRCUM REBAR
268.5SRVCIRCUM REBAR
32.4SRVCIRCUM
29.9SRVCIRCUM
0MWM
268.9AMH4:50AM
268.5SAMSEVERE AGG
268.5MGOMISSING TILES 80% FINISH
73.9SRVLONG CICRUM REBAR
235.5SRVLONG REBAR
59.8SRCLONG CIRCUM REBAR
0MWL
0MGOMH CONN ACTIVE 9:00
117.6SRC
2MGOMISSING TILES 80% START 10:00 TO 2:00
186.8SRCLONG CIRCUM REBAR
160SRVLONG CIRCUM REBAR
38.1SRCLONG CIRCUM REBAR

Properties (6)

custom_field_three
CORRODED LONG CIRCUM REBAR
custom_field_two
2
customer
LACSD
datetime
2016-05-02T01:24:46-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false