Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 2, 2016, 08:22 AM
Date
05/02/2016
W/O
0563402
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00016
PipeID
P00003
Time
1:22 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6698
Sewer Name
08 MAIN STREET TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
07
Purpose
Capital Improvement Program Assesment
Project
20160430MDM_MAIN_STREET_TRUNK
Material
RCP-CTL
Shape
Circular
Height
33 in.
Upstream MH
08 0003
Downstream MH
08 0002
Dir. of Survey
Downstream
Length Surveyed
275.8 ft.
Total Length
275.8 ft.
Structural Index
5
Structural Quick
5K4J
Structural Rating
530
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
5
Overall Quick
Overall Rating
534
Pipe schematic from manhole 08 0003 to 08 0002
MH: 08 0003MH: 08 0002downstream0 ft. AMH - Upstream Manhole, Survey Begins - 3:35AM0 ft. MWL - Water Level, 50 %of cross sectional area0 ft. MGO - General Observation - MH CONN 9:00 STUB0 ft. MWM - Water Mark, 70 %of cross sectional area2 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG3.9 ft. MGO - General Observation - MISSING TILES 20%8.6 ft. MGO - General Observation - MISSING TILES 100% START 10:00 TO 2:009.8 ft. SRV - Surface Reinforcement Visible, from 12 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM17.9 ft. SRV - Surface Reinforcement Visible, from 12 to 02 o'clock, within 8 inches of joint: NO - CIRCUM20.2 ft. SRV - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: YES - CIRCUM22.2 ft. SRV - Surface Reinforcement Visible, from 12 to 02 o'clock, within 8 inches of joint: NO - CIRCUM30.6 ft. MGO - General Observation - MISSING TILES 10%41.4 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR41.4 ft. SRV - Surface Reinforcement Visible, from 12 to 02 o'clock, within 8 inches of joint: YES, Finish - CIRCUM45.1 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR67 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish67 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish67 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR76.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES86.3 ft. MGP - General Photograph97.4 ft. MGO - General Observation - MISSING TILES 10%120.3 ft. MGO - General Observation - TILES MISSING 10%149.7 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR212.5 ft. MGO - General Observation - FEW TILES IN PLACE250.1 ft. MGO - General Observation - FEW TILES IN PLACE265.1 ft. MGO - General Observation - FEW TILES IN PLACE275.1 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - LONG & CIRCUM REBAR275.1 ft. MGO - General Observation - MH CONN ACTIVE 3:00275.1 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG275.1 ft. MGO - General Observation - MH CONN ACTIVE 9:00275.8 ft. AMH - Downstream Manhole, Survey Ends - 4:10AM

Observation photos (17)

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation - MISSING TILES 20%

    3.9 ft. - General Observation - MISSING TILES 20%

  • General Observation - MISSING TILES 100% START 10:00 TO 2:00

    8.6 ft. - General Observation - MISSING TILES 100% START 10:00 TO 2:00

  • Surface Reinforcement Visible, from 12 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM

    9.8 ft. - Surface Reinforcement Visible, from 12 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM

  • Surface Reinforcement Visible, from 12 to 02 o'clock, within 8 inches of joint: NO - CIRCUM

    17.9 ft. - Surface Reinforcement Visible, from 12 to 02 o'clock, within 8 inches of joint: NO - CIRCUM

  • Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: YES - CIRCUM

    20.2 ft. - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: YES - CIRCUM

  • Surface Reinforcement Visible, from 12 to 02 o'clock, within 8 inches of joint: NO - CIRCUM

    22.2 ft. - Surface Reinforcement Visible, from 12 to 02 o'clock, within 8 inches of joint: NO - CIRCUM

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    41.4 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

    45.1 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR

    67 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES

    76.3 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES

  • General Photograph

    86.3 ft. - General Photograph

  • General Observation - MISSING TILES 10%

    97.4 ft. - General Observation - MISSING TILES 10%

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    149.7 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • General Observation - FEW TILES IN PLACE

    212.5 ft. - General Observation - FEW TILES IN PLACE

  • General Observation - FEW TILES IN PLACE

    250.1 ft. - General Observation - FEW TILES IN PLACE

  • General Observation - FEW TILES IN PLACE

    265.1 ft. - General Observation - FEW TILES IN PLACE

Observations (31)

DistanceCodeObservation
97.4MGOMISSING TILES 10%
76.3SRC
120.3MGOTILES MISSING 10%
3.9MGOMISSING TILES 20%
275.1SRCLONG & CIRCUM REBAR
250.1MGOFEW TILES IN PLACE
8.6MGOMISSING TILES 100% START 10:00 TO 2:00
41.4SRVCIRCUM REBAR
212.5MGOFEW TILES IN PLACE
41.4SRVCIRCUM
275.1MGOMH CONN ACTIVE 3:00
149.7SRCCIRCUM REBAR
275.1SAMSEVERE AGG
17.9SRVCIRCUM
45.1SRCLONG CIRCUM REBAR
67SRV
20.2SRVCIRCUM
0AMH3:35AM
2SAMSEVERE AGG
0MWL
0MGOMH CONN 9:00 STUB
275.1MGOMH CONN ACTIVE 9:00
86.3MGP
67SRC
22.2SRVCIRCUM
265.1MGOFEW TILES IN PLACE
9.8SRVCIRCUM
275.8AMH4:10AM
30.6MGOMISSING TILES 10%
0MWM
67SRCLONG & CIRCUM REBAR

Properties (6)

custom_field_three
CORRODED LONG CIRCUM REBAR
custom_field_two
2
customer
LACSD
datetime
2016-05-02T01:22:31-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false