Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 2, 2016, 07:55 AM
Date
05/02/2016
W/O
0563402
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00016
PipeID
P00005
Time
12:55 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6697
Sewer Name
08 MAIN STREET TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
07
Purpose
Capital Improvement Program Assesment
Project
20160430MDM_MAIN_STREET_TRUNK
Material
RCP-CTL
Shape
Circular
Height
33 in.
Upstream MH
08 0005
Downstream MH
08 0004
Dir. of Survey
Downstream
Length Surveyed
275.7 ft.
Total Length
275.7 ft.
Structural Index
5
Structural Quick
5V4J
Structural Rating
792
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
5
Overall Quick
Overall Rating
798
Pipe schematic from manhole 08 0005 to 08 0004
MH: 08 0005MH: 08 0004downstream0 ft. MWL - Water Level, 50 %of cross sectional area0 ft. MGO - General Observation - MH CONN ACTIVE 9:000 ft. MWM - Water Mark, 70 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:55AM2 ft. MGO - General Observation - MISSING TILES 20%% START 10:00 TO 2:009.1 ft. MGO - General Observation - MISSING TILES 100% START 10:00 TO 2:009.1 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG11.2 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES, Start - LONG REBAR11.2 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR14 ft. SRC - Surface Reinforcement Corroded, from 01 to 02 o'clock, within 8 inches of joint: NO - CIRCUM29.2 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES - CIRCUM30.6 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES - CIRCUM33.4 ft. SRC - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: NO - LONG REBAR40.3 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR50.8 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - CIRCUM50.8 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES, Finish - LONG50.8 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM53.1 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES - CORRODED BEYOUND REBAR75.5 ft. MGO - General Observation - MISSING TILES 20%81.7 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM93.8 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO125.5 ft. MGO - General Observation - SMALL AREA OF TILES145.6 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - LONG & CIRCUM REBAR244.8 ft. TBI - Tap Break-In Intruding, at 12 o'clock, -, -, within 8 inches of joint: NO, 8", 3" INTRUDING - ACTIVE275.3 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish - LONG & CIRCUM REBAR275.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR275.3 ft. MGO - General Observation - MISSING TILES 100% FINISH275.3 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG275.7 ft. AMH - Downstream Manhole, Survey Ends - 1:50AM

Observation photos (18)

  • General Observation - MISSING TILES 20%% START 10:00 TO 2:00

    2 ft. - General Observation - MISSING TILES 20%% START 10:00 TO 2:00

  • General Observation - MISSING TILES 100% START 10:00 TO 2:00

    9.1 ft. - General Observation - MISSING TILES 100% START 10:00 TO 2:00

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    9.1 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES, Start - LONG REBAR

    11.2 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES, Start - LONG REBAR

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    11.2 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 01 to 02 o'clock, within 8 inches of joint: NO - CIRCUM

    14 ft. - Surface Reinforcement Corroded, from 01 to 02 o'clock, within 8 inches of joint: NO - CIRCUM

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES - CIRCUM

    29.2 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES - CIRCUM

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES - CIRCUM

    30.6 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES - CIRCUM

  • Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: NO - LONG REBAR

    33.4 ft. - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: NO - LONG REBAR

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR

    40.3 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM

    50.8 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES - CORRODED BEYOUND REBAR

    53.1 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES - CORRODED BEYOUND REBAR

  • General Observation - MISSING TILES 20%

    75.5 ft. - General Observation - MISSING TILES 20%

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM

    81.7 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO

    93.8 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO

  • General Observation - SMALL AREA OF TILES

    125.5 ft. - General Observation - SMALL AREA OF TILES

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - LONG & CIRCUM REBAR

    145.6 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - LONG & CIRCUM REBAR

  • Tap Break-In Intruding, at 12 o'clock, -, -, within 8 inches of joint: NO, 8", 3" INTRUDING - ACTIVE

    244.8 ft. - Tap Break-In Intruding, at 12 o'clock, -, -, within 8 inches of joint: NO, 8", 3" INTRUDING - ACTIVE

Observations (29)

DistanceCodeObservation
9.1MGOMISSING TILES 100% START 10:00 TO 2:00
275.3SRCLONG & CIRCUM REBAR
50.8SRVCIRCUM
50.8SRVLONG
275.3SRCCIRCUM REBAR
275.3MGOMISSING TILES 100% FINISH
11.2SRVLONG REBAR
0MWL
125.5MGOSMALL AREA OF TILES
0MGOMH CONN ACTIVE 9:00
145.6SRCLONG & CIRCUM REBAR
14SRCCIRCUM
0MWM
275.3SAMSEVERE AGG
29.2SRVCIRCUM
50.8SRCCIRCUM
9.1SAMSEVERE AGG
30.6SRVCIRCUM
53.1SRCCORRODED BEYOUND REBAR
2MGOMISSING TILES 20%% START 10:00 TO 2:00
0AMH12:55AM
81.7SRCCIRCUM
40.3SRCLONG & CIRCUM REBAR
93.8SRC
33.4SRCLONG REBAR
75.5MGOMISSING TILES 20%
275.7AMH1:50AM
244.8TBIACTIVE
11.2SRVCIRCUM REBAR

Properties (6)

custom_field_three
CORRODED REBAR-1 AREA CORRODED BEYOUND REBAR
custom_field_two
1
customer
LACSD
datetime
2016-05-02T00:55:00-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false