Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 30, 2016, 08:57 AM
Date
04/30/2016
W/O
0563402
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00016
PipeID
P00006
Time
1:57 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6697
Sewer Name
08 MAIN STREET TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
07
Purpose
Capital Improvement Program Assesment
Project
20160430MDM_MAIN_STREET_TRUNK
Material
RCP-CTL
Shape
Circular
Height
33 in.
Upstream MH
08 0006
Downstream MH
08 0005
Dir. of Survey
Downstream
Length Surveyed
263.7 ft.
Total Length
263.7 ft.
Structural Index
5
Structural Quick
5U41
Structural Rating
554
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
5
Overall Quick
Overall Rating
559
Pipe schematic from manhole 08 0006 to 08 0005
MH: 08 0006MH: 08 0005downstream0 ft. MWM - Water Mark, 80 %of cross sectional area0 ft. MGO - General Observation - MH CONN ACTIVE 9:000 ft. MWL - Water Level, 60 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 7:40AM2 ft. MGO - General Observation - MISSING TILES 60% START2 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES - SEVERE AGG AREAS OF MISSING TILES5 ft. SRV - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: YES - CIRCUM7.6 ft. SRV - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM7.6 ft. SRV - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: NO - CIRCUM11.3 ft. SRV - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM12.3 ft. SRV - Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: YES - CIRCUM12.3 ft. SRV - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: NO - CIRCUM13.5 ft. SRV - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: YES - CIRCUM18.5 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR20.5 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES - CIRCUM21.2 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES, Start - LONG REBAR24.5 ft. MGO - General Observation - MISSING TILES 100% START27.6 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM51.7 ft. MGO - General Observation - MISSING TILES 5%54.1 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM108.3 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM112 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG REBAR177.6 ft. SRC - Surface Reinforcement Corroded, from 11 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR BROKEN263.1 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES, Finish263.1 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish263.7 ft. AMH - Downstream Manhole, Survey Ends - 8:30AM

Observation photos (18)

  • General Observation - MH CONN ACTIVE 9:00

    0 ft. - General Observation - MH CONN ACTIVE 9:00

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES - SEVERE AGG AREAS OF MISSING TILES

    2 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES - SEVERE AGG AREAS OF MISSING TILES

  • Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: YES - CIRCUM

    5 ft. - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: YES - CIRCUM

  • Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM

    7.6 ft. - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM

  • Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: NO - CIRCUM

    7.6 ft. - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: NO - CIRCUM

  • Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM

    11.3 ft. - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM

  • Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: YES - CIRCUM

    12.3 ft. - Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: YES - CIRCUM

  • Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: NO - CIRCUM

    12.3 ft. - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: NO - CIRCUM

  • Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: YES - CIRCUM

    13.5 ft. - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: YES - CIRCUM

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    18.5 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES - CIRCUM

    20.5 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES - CIRCUM

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES, Start - LONG REBAR

    21.2 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES, Start - LONG REBAR

  • General Observation - MISSING TILES 100% START

    24.5 ft. - General Observation - MISSING TILES 100% START

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM

    27.6 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM

    54.1 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM

    108.3 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG REBAR

    112 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG REBAR

  • Surface Reinforcement Corroded, from 11 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR BROKEN

    177.6 ft. - Surface Reinforcement Corroded, from 11 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR BROKEN

Observations (26)

DistanceCodeObservation
27.6SRVCIRCUM
263.1SRV
108.3SRVCIRCUM
2MGOMISSING TILES 60% START
11.3SRVCIRCUM
24.5MGOMISSING TILES 100% START
13.5SRVCIRCUM
51.7MGOMISSING TILES 5%
263.1SRV
112SRVLONG REBAR
12.3SRVCIRCUM
21.2SRVLONG REBAR
263.7AMH8:30AM
20.5SRVCIRCUM
5SRVCIRCUM
54.1SRVCIRCUM
0MWM
0MGOMH CONN ACTIVE 9:00
12.3SRVCIRCUM
7.6SRVCIRCUM
0MWL
2SAMSEVERE AGG AREAS OF MISSING TILES
7.6SRVCIRCUM
0AMH7:40AM
18.5SRVCIRCUM REBAR
177.6SRCCIRCUM REBAR BROKEN

Properties (6)

custom_field_three
VISIBLE REBAR LONG & CIRCUM - 1 BROKEN
custom_field_two
1
customer
LACSD
datetime
2016-04-30T01:57:30-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false