Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 30, 2016, 08:35 AM
Date
04/30/2016
W/O
0563839
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00016
PipeID
P00011
Time
1:35 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6696
Sewer Name
08 MAIN STREET TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
07
Purpose
Capital Improvement Program Assesment
Project
20160430MDM_MAIN_STREET_TRUNK
Material
RCP-CTL
Shape
Circular
Height
33 in.
Upstream MH
08 0011
Downstream MH
08 0010
Dir. of Survey
Downstream
Length Surveyed
264.7 ft.
Total Length
264.7 ft.
Structural Index
4
Structural Quick
5B41
Structural Rating
213
O&M Index
2
O&M Quick
422G
O&M Rating
88
Overall Index
3
Overall Quick
Overall Rating
301
Pipe schematic from manhole 08 0011 to 08 0010
MH: 08 0011MH: 08 0010downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:00AM0 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. MGO - General Observation - MISSING TILES 20% START2 ft. MGO - General Observation - MAG COAT 50% START 9:00 TO 3:0055.9 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES57.7 ft. MGO - General Observation - NEW MISSING TILES 2:0063.3 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start72.1 ft. SAP - Surface Aggregate Projecting, from 12 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG75.7 ft. SRV - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR84.4 ft. MGO - General Observation - MISSING TILES 100% 9:00 TO 3:0084.4 ft. DSZ - Deposits Settled Other, 30 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO - FALLEN TILES101.4 ft. MGO - General Observation - MISSING TILES 100%148 ft. MGO - General Observation - MISSING TILES 80%149.3 ft. SAM - Surface Aggregate Missing, from 01 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG168.2 ft. SRV - Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR168.2 ft. MGO - General Observation - MISSING TILES 80%173.9 ft. SRV - Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: YES - CIRCUM REBAR186.4 ft. MGO - General Observation - MISSING TILES 100%START190.8 ft. SRV - Surface Reinforcement Visible, from 01 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR195.1 ft. SRV - Surface Reinforcement Visible, from 01 to 03 o'clock, within 8 inches of joint: YES, Finish201 ft. SRV - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: NO - CIRCUM203.2 ft. MGO - General Observation - 100% MISSING TILES FINISH215.7 ft. SRV - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: YES - CIRCUM218 ft. MGO - General Observation - MISSING TILES 90% START 10: TO 2:00229.7 ft. SRV - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: YES - CIRCUM232.1 ft. SRV - Surface Reinforcement Visible, at 10 o'clock, within 8 inches of joint: YES - CIRCUM REBAR234.7 ft. SRV - Surface Reinforcement Visible, from 01 to 03 o'clock, within 8 inches of joint: NO, Start - CIRCUM239 ft. SRV - Surface Reinforcement Visible, from 01 to 03 o'clock, within 8 inches of joint: NO, Finish251.5 ft. SRV - Surface Reinforcement Visible, from 01 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM252.2 ft. SRV - Surface Reinforcement Visible, from 08 to 10 o'clock, within 8 inches of joint: YES - CIRCUM257.2 ft. SRV - Surface Reinforcement Visible, from 01 to 03 o'clock, within 8 inches of joint: NO264.2 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish264.2 ft. MGO - General Observation - MISSING TILES 90% FINISH264.2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG264.2 ft. SRV - Surface Reinforcement Visible, from 01 to 03 o'clock, within 8 inches of joint: YES, Finish - CIRCUM264.2 ft. MGO - General Observation - MAG COAT 50% FINISH264.7 ft. AMH - Downstream Manhole, Survey Ends - 3:40AM

Observation photos (24)

  • General Observation - MISSING TILES 20% START

    2 ft. - General Observation - MISSING TILES 20% START

  • General Observation - MAG COAT 50% START 9:00 TO 3:00

    2 ft. - General Observation - MAG COAT 50% START 9:00 TO 3:00

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES

    55.9 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES

  • General Observation - NEW MISSING TILES 2:00

    57.7 ft. - General Observation - NEW MISSING TILES 2:00

  • Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    63.3 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 12 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

    72.1 ft. - Surface Aggregate Projecting, from 12 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    75.7 ft. - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • General Observation - MISSING TILES 100% 9:00 TO 3:00

    84.4 ft. - General Observation - MISSING TILES 100% 9:00 TO 3:00

  • General Observation - MISSING TILES 100%

    101.4 ft. - General Observation - MISSING TILES 100%

  • General Observation - MISSING TILES 80%

    148 ft. - General Observation - MISSING TILES 80%

  • Surface Aggregate Missing, from 01 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG

    149.3 ft. - Surface Aggregate Missing, from 01 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG

  • Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    168.2 ft. - Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    173.9 ft. - Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • General Observation - MISSING TILES 100%START

    186.4 ft. - General Observation - MISSING TILES 100%START

  • Surface Reinforcement Visible, from 01 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    190.8 ft. - Surface Reinforcement Visible, from 01 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: NO - CIRCUM

    201 ft. - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: NO - CIRCUM

  • Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: YES - CIRCUM

    215.7 ft. - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: YES - CIRCUM

  • General Observation - MISSING TILES 90% START 10: TO 2:00

    218 ft. - General Observation - MISSING TILES 90% START 10: TO 2:00

  • Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: YES - CIRCUM

    229.7 ft. - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: YES - CIRCUM

  • Surface Reinforcement Visible, at 10 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    232.1 ft. - Surface Reinforcement Visible, at 10 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Surface Reinforcement Visible, from 01 to 03 o'clock, within 8 inches of joint: NO, Start - CIRCUM

    234.7 ft. - Surface Reinforcement Visible, from 01 to 03 o'clock, within 8 inches of joint: NO, Start - CIRCUM

  • Surface Reinforcement Visible, from 01 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM

    251.5 ft. - Surface Reinforcement Visible, from 01 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM

  • Surface Reinforcement Visible, from 08 to 10 o'clock, within 8 inches of joint: YES - CIRCUM

    252.2 ft. - Surface Reinforcement Visible, from 08 to 10 o'clock, within 8 inches of joint: YES - CIRCUM

  • Surface Reinforcement Visible, from 01 to 03 o'clock, within 8 inches of joint: NO

    257.2 ft. - Surface Reinforcement Visible, from 01 to 03 o'clock, within 8 inches of joint: NO

Observations (38)

DistanceCodeObservation
264.7AMH3:40AM
201SRVCIRCUM
84.4MGOMISSING TILES 100% 9:00 TO 3:00
232.1SRVCIRCUM REBAR
218MGOMISSING TILES 90% START 10: TO 2:00
239SRV
234.7SRVCIRCUM
148MGOMISSING TILES 80%
252.2SRVCIRCUM
229.7SRVCIRCUM
0MWL
195.1SRV
63.3DAGS
149.3SAMSEVERE AGG
72.1SAPSEVERE AGG
215.7SRVCIRCUM
101.4MGOMISSING TILES 100%
251.5SRVCIRCUM
190.8SRVCIRCUM REBAR
264.2DAGS
264.2MGOMISSING TILES 90% FINISH
264.2SAVSEVERE AGG
257.2SRV
57.7MGONEW MISSING TILES 2:00
2MGOMISSING TILES 20% START
2MGOMAG COAT 50% START 9:00 TO 3:00
75.7SRVCIRCUM REBAR
168.2SRVCIRCUM REBAR
264.2SRVCIRCUM
173.9SRVCIRCUM REBAR
264.2MGOMAG COAT 50% FINISH
0AMH3:00AM
186.4MGOMISSING TILES 100%START
203.2MGO100% MISSING TILES FINISH
0MWM
84.4DSZFALLEN TILES
168.2MGOMISSING TILES 80%
55.9SAVSEVERE AGG AREAS OF MISSING TILES

Properties (6)

custom_field_three
CIRCUM REBAR VISIBLE
custom_field_two
2
customer
LACSD
datetime
2016-04-30T01:35:46-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false