Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 28, 2016, 09:24 AM
  • C 0119_C 0118_4282016_025315.mp4

Date
04/28/2016
W/O
0561707
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00127
PipeID
P09639
Time
2:24 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0117
Sewer Name
C JOINT OUTFALL C - UNIT 4B
City
LONG BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
20
Purpose
Maintenance Related
Project
20160428MDM_JOINT_OUTFALL_C_UNIT_4B
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Upstream MH
C 0119
Downstream MH
C 0118
Dir. of Survey
Downstream
Length Surveyed
438.6 ft.
Total Length
438.6 ft.
Structural Index
4
Structural Quick
5541
Structural Rating
42
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
4
Overall Quick
Overall Rating
45
Pipe schematic from manhole C 0119 to C 0118
MH: C 0119MH: C 0118downstream0 ft. MGO - General Observation - MH CONN 9:30 ACTIVE0 ft. MGO - General Observation - MH CONN UNDER FLOW 9:00 -UNKNOWN0 ft. MGO - General Observation - MH CONN UNDER FLOW 3:00 UNKNOWN0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:25AM0 ft. MWM - Water Mark, 20 %of cross sectional area1 ft. MGO - General Observation - MH ROLLER SHEVE & POLE USED MH#A247 DIVERTING MORE FLOW2 ft. MGO - General Observation - 48" RCP2.7 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES, Start - LONG REBAR2.7 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERER AGG2.7 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR6.9 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO - CIRCUM9.1 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES - CORRODED BEYOUND REBAR10.4 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR10.4 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES, Finish - LONG REBAR13.1 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR13.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG13.1 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG13.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING CONCRETE23.5 ft. MGO - General Observation - 48" RCP61.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING &BLISTERING LAITANCE COAT69.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active69.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC69.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG69.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish261.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Active298 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active298.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - VERY SPORATIC310.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG SPORATIC342.6 ft. MGP - General Photograph428 ft. DSZ - Deposits Settled Other, 20 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES - FLOATING DEBRIE438.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG VERY SPORATIC438.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING LAITANCE COAT438.1 ft. MGO - General Observation - VEIW DOWNLEG UPSTREAM SIPHON438.6 ft. AMH - Downstream Manhole, Survey Ends - 3:45AM

Observation photos (17)

  • General Observation - MH CONN UNDER FLOW 9:00 -UNKNOWN

    0 ft. - General Observation - MH CONN UNDER FLOW 9:00 -UNKNOWN

  • General Observation - MH CONN UNDER FLOW 3:00 UNKNOWN

    0 ft. - General Observation - MH CONN UNDER FLOW 3:00 UNKNOWN

  • General Observation - 48" RCP

    2 ft. - General Observation - 48" RCP

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES, Start - LONG REBAR

    2.7 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES, Start - LONG REBAR

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERER AGG

    2.7 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERER AGG

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    2.7 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO - CIRCUM

    6.9 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO - CIRCUM

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES - CORRODED BEYOUND REBAR

    9.1 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES - CORRODED BEYOUND REBAR

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    13.1 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING CONCRETE

    13.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING CONCRETE

  • General Observation - 48" RCP

    23.5 ft. - General Observation - 48" RCP

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING &BLISTERING LAITANCE COAT

    61.2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING &BLISTERING LAITANCE COAT

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    69.8 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - VERY SPORATIC

    298.3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - VERY SPORATIC

  • General Photograph

    342.6 ft. - General Photograph

  • Deposits Settled Other,  20 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES - FLOATING DEBRIE

    428 ft. - Deposits Settled Other, 20 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES - FLOATING DEBRIE

  • General Observation - VEIW DOWNLEG UPSTREAM SIPHON

    438.1 ft. - General Observation - VEIW DOWNLEG UPSTREAM SIPHON

Observations (35)

DistanceCodeObservation
23.5MGO48" RCP
261.3TFActive
1MGOMH ROLLER SHEVE & POLE USED MH#A247 DIVERTING MORE FLOW
438.1SAVSEVERE AGG VERY SPORATIC
61.2SSSPEELING &BLISTERING LAITANCE COAT
310.8SAVSEVERE AGG SPORATIC
0MGOMH CONN 9:30 ACTIVE
10.4SRVCIRCUM REBAR
6.9SRCCIRCUM
2MGO48" RCP
69.8TFActive
69.8SAVSEVERE AGG SPORATIC
298TFActive
10.4SRVLONG REBAR
13.1SRVCIRCUM REBAR
69.8SAPSEVERE AGG
13.1SAPSEVERE AGG
2.7SRVLONG REBAR
298.3SAVVERY SPORATIC
438.1SSSBLISTERING PEELING LAITANCE COAT
428DSZFLOATING DEBRIE
2.7SAMSEVERER AGG
342.6MGP
13.1SAMSEVERE AGG
13.1SSSBLISTERING CONCRETE
0MGOMH CONN UNDER FLOW 9:00 -UNKNOWN
0MGOMH CONN UNDER FLOW 3:00 UNKNOWN
9.1SRCCORRODED BEYOUND REBAR
69.8SSS
438.6AMH3:45AM
0MWL
438.1MGOVEIW DOWNLEG UPSTREAM SIPHON
2.7SRVCIRCUM REBAR
0AMH2:25AM
0MWM

Properties (6)

custom_field_three
REBAR CORRODED-CORRODED BEYOUND REBAR-FRIST 13'
custom_field_two
1
customer
LACSD
datetime
2016-04-28T02:24:14-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false