- Date
- 04/29/2016
- W/O
- 0563396
- Weather
- Dry
- Operator/Surveyor
- MIRANDA
- Sewer ID
- Z00689
- PipeID
- P25325
- Time
- 10:01 AM
- Certificate
- U-1014-06022542
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- G7101
- Sewer Name
- 18 MILLS AVENUE TRUNK
- City
- WHITTIER
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 18
- Page No.
- 21
- Purpose
- Routine Assessment
- Project
- 20160428AM_MILLS_AVENUE_TRUNK
- Material
- NRCP
- Shape
- Circular
- Height
- 12 in.
- Upstream MH
- 18 0058
- Downstream MH
- 18 0057
- Dir. of Survey
- Downstream
- Length Surveyed
- 234.6 ft.
- Total Length
- 234.6 ft.
- Structural Index
- 4
- Structural Quick
- 4431
- Structural Rating
- 21
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 4
- Overall Quick
- —
- Overall Rating
- 21
Pipe schematic from manhole 18 0058 to 18 0057 Observation photos (5)

4.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

89.6 ft. - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: YES, 4"

149 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

203.7 ft. - Broken, from 11 to 01 o'clock, within 8 inches of joint: YES

203.7 ft. - General Photograph - BROKEN