Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 15, 2016, 03:59 PM
  • _29 0461_4152016_091910.mp4

Date
04/15/2016
W/O
0547103
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00989
PipeID
P24505
Time
8:59 AM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7092
Sewer Name
29 LEWIS AVENUE SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
03
Purpose
Routine Assessment
Project
20160415AM_LEWIS_AVENUE_SEWER
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Upstream MH
29 0461
Dir. of Survey
Upstream
Length Surveyed
359.7 ft.
Total Length
359.7 ft.
Structural Index
3
Structural Quick
5243
Structural Rating
60
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
64
Pipe schematic from manhole 29 0461 to unknown
MH: 29 0461MH: upstream0 ft. AMH - Upstream Manhole, Survey Ends - 10:10 AM0.7 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"48.8 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES53.3 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: YES, 6"56 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"58.6 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"70.1 ft. CM - Crack Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES105.1 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"106.6 ft. B - Broken, from 08 to 11 o'clock, within 8 inches of joint: YES140.9 ft. FM - Fracture Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES152.3 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"154.9 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"158.9 ft. CL - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES176.6 ft. MGO - General Observation - CHIPPING @ 11 O'CLOCK177.2 ft. MGO - General Observation - CHIPPING @ 08 O'CLOCK186.3 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES192.2 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES195 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES201 ft. CL - Crack Longitudinal, at 05 o'clock, within 8 inches of joint: YES201.3 ft. CM - Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES205.3 ft. TFD - Tap Factory Made Defective, at 03 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE, OFFSET206.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES208 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 6" - OPEN245.2 ft. CM - Crack Multiple, from 08 to 01 o'clock, within 8 inches of joint: YES252.8 ft. TFD - Tap Factory Made Defective, at 09 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE, OFFSET253.9 ft. JSM - Joint Separated Medium254.1 ft. CM - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES255.6 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: YES, 6"298.9 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES331.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES332.8 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: YES, 6"334.4 ft. MGP - General Photograph - BROKEN PIPE334.4 ft. BSV - Broken Soil Visible, from 03 to 04 o'clock, within 8 inches of joint: YES334.6 ft. FM - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES335.8 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: YES, 6"345.2 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES351.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES354.7 ft. JOL - Joint Offset Large359.7 ft. MWL - Water Level, 5 %of cross sectional area359.7 ft. AMH - Downstream Manhole, Survey Begins - 9:18 AM359.7 ft. MGO - General Observation - ROACHES INSIDE THE MH.359.7 ft. MWM - Water Mark, 10 %of cross sectional area

Observation photos (12)

  • Joint Offset Large

    5 ft. - Joint Offset Large

  • Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

    25.1 ft. - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

  • General Photograph - BROKEN PIPE

    25.3 ft. - General Photograph - BROKEN PIPE

  • Broken Soil Visible, from 03 to 04 o'clock, within 8 inches of joint: YES

    25.3 ft. - Broken Soil Visible, from 03 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    28 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Joint Separated Medium

    105.8 ft. - Joint Separated Medium

  • Tap Factory Made Defective, at 09 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE, OFFSET

    106.9 ft. - Tap Factory Made Defective, at 09 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE, OFFSET

  • Tap Factory Made Defective, at 03 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE, OFFSET

    154.4 ft. - Tap Factory Made Defective, at 03 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE, OFFSET

  • Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    164.7 ft. - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • General Observation - CHIPPING @ 08 O'CLOCK

    182.5 ft. - General Observation - CHIPPING @ 08 O'CLOCK

  • General Observation - CHIPPING @ 11 O'CLOCK

    183.1 ft. - General Observation - CHIPPING @ 11 O'CLOCK

  • Broken, from 08 to 11 o'clock, within 8 inches of joint: YES

    253.1 ft. - Broken, from 08 to 11 o'clock, within 8 inches of joint: YES

Observations (43)

DistanceCodeObservation
0MWL
0AMH9:18 AM
253.1B
106.9TFDACTIVE, OFFSET
25.1FM
105.6CM
23.9TFA
152.8CM
218.8FM
207.4TFC
154.4TFDACTIVE, OFFSET
182.5MGOCHIPPING @ 08 O'CLOCK
104.1TFC
0MGOROACHES INSIDE THE MH.
164.7FL
301.1TFA
26.9TFA
151.7TFOPEN
25.3MGPBROKEN PIPE
359TFC
0MWM
14.5CL
356.7TFC
183.1MGOCHIPPING @ 11 O'CLOCK
158.7CL
173.4CM
105.8JSM
254.6TFC
306.4TFC
167.5CL
158.4CM
289.6CM
204.8TFA
114.5CM
8.3CL
60.8CL
5JOL
359.7AMH10:10 AM
25.3BSV
310.9CL
303.7TFA
28FM
200.8CL

Properties (6)

custom_field_three
BROKEN PIPE
custom_field_two
1
customer
LACSD
datetime
2016-04-15T08:59:48-07:00
documentation
MIRANDA, FRANKLIN, SHADLER
is_lateral_inspection
false