Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 5, 2016, 09:13 AM
  • 05 1075_05 1074_04052016_Manual.mp4

Date
04/05/2016
W/O
0557603
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00488
PipeID
P06309
Time
2:13 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6677
Sewer Name
05 MONETA EXTENSION TRUNK, SECTION 1
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
21
Purpose
Routine Assessment
Project
20160405MDM_MONETA_EXTENSION_TRUNK_SECTION_1
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
05 1075
Downstream MH
05 1074
Dir. of Survey
Downstream
Length Surveyed
221.3 ft.
Total Length
221.3 ft.
Structural Index
2
Structural Quick
2312
Structural Rating
8
O&M Index
2
O&M Quick
412H
O&M Rating
94
Overall Index
2
Overall Quick
Overall Rating
102
Pipe schematic from manhole 05 1075 to 05 1074
MH: 05 1075MH: 05 1074downstream0 ft. AMH - Upstream Manhole, Survey Begins - 3:20AM0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - MH CONN ACTIVE 3:000 ft. MGO - General Observation - MH CONN STUB 9:002 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2.3 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 08 to 09 o'clock, , within 8 inches of joint: NO79.1 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES112 ft. CC - Crack Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES121.3 ft. MGO - General Observation - 24" VCP141.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE184.6 ft. CC - Crack Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES184.6 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES201 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES221.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish221.1 ft. MGO - General Observation - MH CONN ACTIVE 3:00221.3 ft. AMH - Downstream Manhole, Survey Ends - 3:40AM

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - 24" VCP

    121.3 ft. - General Observation - 24" VCP

Observations (17)

DistanceCodeObservation
221.1DAGS
184.6CC
0AMH3:20AM
112CC
121.3MGO24" VCP
2.3DAGS
0MWM
0MWL
201CL
184.6CL
79.1CL
2DAGS
141.5TFACTIVE
221.1MGOMH CONN ACTIVE 3:00
0MGOMH CONN ACTIVE 3:00
0MGOMH CONN STUB 9:00
221.3AMH3:40AM

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2016-04-05T02:13:52-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false