Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 1, 2016, 08:17 AM
  • 05 1085_05 1084_412016_022431.mp4

Date
04/01/2016
W/O
0557603
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00488
PipeID
P06319
Time
1:17 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0106
Sewer Name
05 MONETA EXTENSION TRUNK, SECTION 1
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
18
Purpose
Routine Assessment
Project
20160401MDM_MONETA_EXTENSION_TRUNK_SECTION_1
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
05 1085
Downstream MH
05 1084
Dir. of Survey
Downstream
Length Surveyed
476.8 ft.
Total Length
476.8 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 05 1085 to 05 1084
MH: 05 1085MH: 05 1084downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - MH CONN STUB 3:000 ft. AMH - Upstream Manhole, Survey Begins - 1:55AM2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start6 ft. MGO - General Observation - 24" VCP244.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"251.6 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES343.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"425.7 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES - HAIRLINE476.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish476.8 ft. AMH - Downstream Manhole, Survey Ends - 2:35AM

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - 24" VCP

    6 ft. - General Observation - 24" VCP

Observations (12)

DistanceCodeObservation
343.4TFC
0MWL
476.5DAGS
425.7FLHAIRLINE
476.8AMH2:35AM
0MWM
0MGOMH CONN STUB 3:00
2DAGS
244.9TFC
6MGO24" VCP
251.6CL
0AMH1:55AM

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2016-04-01T01:17:39-07:00
documentation
MARTIN,MANANES,REVELES
is_lateral_inspection
false