Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 1, 2016, 07:32 AM
  • 05 1087_05 1086_412016_004215.mp4

  • 05 1087_05 1086_412016_004729.mp4

Date
04/01/2016
W/O
0557603
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00488
PipeID
P06321
Time
12:32 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0106
Sewer Name
05 MONETA EXTENSION TRUNK, SECTION 1
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
18
Purpose
Routine Assessment
Project
20160401MDM_MONETA_EXTENSION_TRUNK_SECTION_1
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
05 1087
Downstream MH
05 1086
Dir. of Survey
Downstream
Length Surveyed
439.9 ft.
Total Length
439.9 ft.
Structural Index
1
Structural Quick
1300
Structural Rating
3
O&M Index
2
O&M Quick
2400
O&M Rating
8
Overall Index
2
Overall Quick
Overall Rating
11
Pipe schematic from manhole 05 1087 to 05 1086
MH: 05 1087MH: 05 1086downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:35AM0 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start18.7 ft. DSGV - Deposits Settled Gravel, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: NO41.8 ft. DSGV - Deposits Settled Gravel, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES104.7 ft. CC - Crack Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES127.2 ft. CC - Crack Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES149.9 ft. CC - Crack Circumferential, from 11 to 04 o'clock, within 8 inches of joint: YES150.1 ft. MGO - General Observation - 24" VCP384.6 ft. DSGV - Deposits Settled Gravel, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES439 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish439 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active439 ft. MGO - General Observation - MH CONN STUB 2:00439.9 ft. AMH - Downstream Manhole, Survey Ends - 1:10AM

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - 24" VCP

    150.1 ft. - General Observation - 24" VCP

Observations (15)

DistanceCodeObservation
0MWL
0AMH12:35AM
127.2CC
41.8DSGV
149.9CC
439DAGS
104.7CC
18.7DSGV
0MWM
2DAGS
384.6DSGV
439.9AMH1:10AM
150.1MGO24" VCP
439MGOConn. @ Mh, 3 O' Clock. Active
439MGOMH CONN STUB 2:00

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2016-04-01T00:32:58-07:00
documentation
MARTIN,MANANES,REVELES
is_lateral_inspection
false