Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 22, 2021, 11:20 AM
  • 01 0442_01 0441_3222021_042344.mp4

Date
03/22/2021
W/O
0880122
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00208
PipeID
P00924
Time
4:20 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1754
Sewer Name
01 HOLMES-WILLOWBROOK TRUNK
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Capital Improvement Program Assesment
Project
20210322MDM_HOLMES_WILLOWBROOK_TRUNK
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
01 0442
Downstream MH
01 0441
Dir. of Survey
Downstream
Length Surveyed
346.7 ft.
Total Length
346.7 ft.
Structural Index
3
Structural Quick
4326
Structural Rating
24
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
28
Pipe schematic from manhole 01 0442 to 01 0441
MH: 01 0442MH: 01 0441downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:20AM0 ft. MWM - Water Mark, 55 %of cross sectional area2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVBERE AGG2 ft. MGO - General Observation - MAG COAT 90% START19.9 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SLIGHT28.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open32.6 ft. MWM - Water Mark, 30 %of cross sectional area35.8 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG37.7 ft. MGO - General Observation - 60% MAG COAT START45.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE67.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open77.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active80.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE80.1 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG80.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped80.1 ft. MGO - General Observation - 90% MAG COAT START80.1 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG80.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE80.1 ft. MWM - Water Mark, 20 %of cross sectional area93.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open127.4 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active136.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open139.2 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped182.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open193.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open201.1 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Open219 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Open222.2 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SLIGHT244.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open267.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped274.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open291.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open317 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - PEELING CONCRETE321.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open342.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open346.3 ft. MGO - General Observation - 90% MAG COAT FINISH346.3 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG346.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE UNDER MAG COAT346.7 ft. AMH - Downstream Manhole, Survey Ends - 4:55AM

Observation photos (9)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVBERE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVBERE AGG

  • General Observation - MAG COAT 90% START

    2 ft. - General Observation - MAG COAT 90% START

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

    35.8 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • General Observation - 60% MAG COAT START

    37.7 ft. - General Observation - 60% MAG COAT START

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

    45.9 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

  • General Observation - 90% MAG COAT START

    80.1 ft. - General Observation - 90% MAG COAT START

  • Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SLIGHT

    222.2 ft. - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SLIGHT

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - PEELING CONCRETE

    317 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - PEELING CONCRETE

Observations (41)

DistanceCodeObservation
342.3TFOpen
80.1SSSBLISTERING PEELING CONCRETE
321.6TFOpen
80.1SAMSEVERE AGG
93.1TFOpen
2SSSBLISTERING PEELING CONCRETE UNDER MAG COAT
346.3MGO90% MAG COAT FINISH
274.1TFOpen
2SAMSEVBERE AGG
28.9TFOpen
193.1TFOpen
0MWL
80.1TFCCapped
80.1MGO90% MAG COAT START
67.6TFOpen
136.3TFOpen
139.2TFCCapped
32.6MWM
267.7TFCCapped
317SSSPEELING CONCRETE
2MGOMAG COAT 90% START
37.7MGO60% MAG COAT START
77.6TFActive
346.7AMH4:55AM
346.3SAMSEVERE AGG
80.1SAMSEVERE AGG
80.1SSSBLISTERING PEELING CONCRETE
291.1TFOpen
35.8SAMSEVERE AGG
0AMH4:20AM
0MWM
201.1TFOpen
80.1MWM
244.8TFOpen
45.9SSSBLISTERING PEELING CONCRETE
222.2FCSLIGHT
346.3SSSBLISTERING PEELING CONCRETE UNDER MAG COAT
219TFOpen
182.6TFOpen
19.9FCSLIGHT
127.4TBActive

Properties (6)

custom_field_three
SEVERE AGG MISSING
custom_field_two
2
customer
LACSD
datetime
2021-03-22T04:20:08-07:00
documentation
MARTIN,CASTILLO,RUVALCABA
is_lateral_inspection
false