Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 28, 2021, 09:25 AM
  • 05 0499A_05 0499_01282021_014216.mp4

Date
01/28/2021
W/O
870604
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00459
PipeID
P05716
Time
1:25 AM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8511
Sewer Name
05 INGLEWOOD TRUNK #1
City
INGLEWOOD
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
04
Purpose
Routine Assessment
Project
WO_870604_TV05042_JAN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
36 in.
Upstream MH
05 0499A
Downstream MH
05 0499
Dir. of Survey
Downstream
Length Surveyed
169.9 ft.
Total Length
170 ft.
Structural Index
3
Structural Quick
3B00
Structural Rating
42
O&M Index
2
O&M Quick
2F00
O&M Rating
66
Overall Index
2
Overall Quick
Overall Rating
108
Pipe schematic from manhole 05 0499A to 05 0499
MH: 05 0499AMH: 05 0499downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 0499A0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start7.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4" - OPEN52.1 ft. LFW - Lining Failure Wrinkled, at 12 o'clock, within 8 inches of joint: YES, Start112.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"122.9 ft. LFW - Lining Failure Wrinkled, at 12 o'clock, within 8 inches of joint: YES, Finish165 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 4" - OPEN168.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish170 ft. AMH - Downstream Manhole, Survey Ends - 05 0499

Observation photos (1)

  • Lining Failure Wrinkled, at 12 o'clock, within 8 inches of joint: YES, Start

    52.1 ft. - Lining Failure Wrinkled, at 12 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
165TFOPEN
7.3TFOPEN
112.3TFC
52.1LFW
0AMH05 0499A
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
168.2DAGS
2DAGS
0MWL
122.9LFW
0MWM
170AMH05 0499

Properties (8)

additional_info
630138012721201
custom_field_three
GREASE
custom_field_two
4
customer
1
datetime
2021-01-28T01:25:29-08:00
documentation
PRO PIPE
is_lateral_inspection
false
lining
CIPP