Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 28, 2021, 11:30 AM
  • 05 0496_05 0495_01282021_035013.mp4

Date
01/28/2021
W/O
870604
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00459
PipeID
P05712
Time
3:30 AM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8511
Sewer Name
05 INGLEWOOD TRUNK #1
City
INGLEWOOD
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
04
Purpose
Routine Assessment
Project
WO_870604_TV05042_JAN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
24 in.
Upstream MH
05 0496
Downstream MH
05 0495
Dir. of Survey
Downstream
Length Surveyed
290.4 ft.
Total Length
290.4 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2J00
O&M Rating
114
Overall Index
2
Overall Quick
Overall Rating
114
Pipe schematic from manhole 05 0496 to 05 0495
MH: 05 0496MH: 05 0495downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 04960 ft. MWL - Water Level, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start48.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4" - OPEN56.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4" - OPEN106.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4" - OPEN133.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4" - OPEN168.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4" - OPEN183.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4" - OPEN216 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4" - OPEN233.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4" - OPEN265.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4" - OPEN283 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4", 4" - OPEN288.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish290.4 ft. AMH - Downstream Manhole, Survey Ends - 05 0495

Observations (16)

DistanceCodeObservation
233.5TFOPEN
283TFOPEN
133.7TFOPEN
216TFOPEN
0MWM
0AMH05 0496
290.4AMH05 0495
106.2TFOPEN
265.7TFOPEN
48.7TFOPEN
0MWL
56.3TFOPEN
168.7TFOPEN
2DAGS
183.9TFOPEN
288.3DAGS

Properties (8)

additional_info
630138012721201
custom_field_three
GREASE
custom_field_two
4
customer
1
datetime
2021-01-28T03:30:50-08:00
documentation
PRO PIPE
is_lateral_inspection
false
lining
CIPP