Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 5, 2021, 06:32 AM
  • 05 0489A_05 0489_02042021_224420.mp4

Date
02/04/2021
W/O
870604
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00459
PipeID
P05704
Time
10:32 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8466
Sewer Name
05 INGLEWOOD TRUNK #1
City
INGLEWOOD
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
04
Purpose
Routine Assessment
Project
WO_870604_TV05042_JAN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
24 in.
Upstream MH
05 0489A
Downstream MH
05 0489
Dir. of Survey
Downstream
Length Surveyed
265.6 ft.
Total Length
265.6 ft.
Structural Index
2
Structural Quick
2I00
Structural Rating
104
O&M Index
2
O&M Quick
2J00
O&M Rating
106
Overall Index
2
Overall Quick
Overall Rating
210
Pipe schematic from manhole 05 0489A to 05 0489
MH: 05 0489AMH: 05 0489downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/UNKNOWN0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 0489A2 ft. MWLS - Water Level, Sag in pipe, 10 %of cross sectional area, Start2.7 ft. MGO - General Observation - PIPE IS LINED2.7 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start36.3 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - 30% ROOTS/OPEN38.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"99.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"131.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN184.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN263 ft. MWLS - Water Level, Sag in pipe, 10 %of cross sectional area, Finish264.6 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish265 ft. MGO - General Observation - ROACHES @ MH265.6 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE265.6 ft. AMH - Downstream Manhole, Survey Ends - 05 0489265.6 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE

Observation photos (1)

  • Deposits Attached Grease, 10 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    2.7 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

Observations (18)

DistanceCodeObservation
265.6MGOCONN @ MH 3 O'CLOCK/ACTIVE
265.6AMH05 0489
36.3TFD30% ROOTS/OPEN
2.7MGOPIPE IS LINED
0MWM
0MGOCONN @ MH 3 O'CLOCK/UNKNOWN
0MWL
264.6DAGS
131.7TFOPEN
99.3TFC
2MWLS
0AMH05 0489A
2.7DAGS
265MGOROACHES @ MH
38.8TFC
265.6MGOCONN @ MH 9 O'CLOCK/ACTIVE
184.8TFOPEN
263MWLS

Properties (8)

additional_info
630074020421201
custom_field_three
NO SEVERE DEFECTS
custom_field_two
4
customer
1
datetime
2021-02-04T22:32:06-08:00
documentation
PRO PIPE
is_lateral_inspection
false
lining
CIPP